HISTORY LOG 1 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS MON 10:49AM 11/14/16 CHILLED LEAVING= 43.3~F; RETURN= 50.1~F EVAP = 34.1 PSIG; COND = 84.2 PSIG OIL PRESSURE = 38.5 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 75.1~F; RETURN = 69.8~F MOTOR CURRENT = 57 %FLA OPER. HOURS =44027; START COUNTER = 1993 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 38.9~F, COND= 78.4~F DISCHARGE TEMP=102.0~F,OIL TEMP=113.4~F HOP = 67.0 PSIG; LOP = 31.1 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON MON 10:49AM FLOW SWITCH-AUTOSTART  HISTORY LOG 2 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS MON 10:19AM 11/14/16 CHILLED LEAVING= 43.1~F; RETURN= 50.1~F EVAP = 37.1 PSIG; COND = 82.4 PSIG OIL PRESSURE = 14.0 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 76.8~F; RETURN = 69.5~F MOTOR CURRENT = 122 %FLA OPER. HOURS =44027; START COUNTER = 1992 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 40.9~F, COND= 79.0~F DISCHARGE TEMP=102.9~F,OIL TEMP=112.8~F HOP = 44.6 PSIG; LOP = 33.3 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - ON REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF MON 10:19AM LOW OIL PRESSURE  HISTORY LOG 3 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS SUN 8:25AM 11/13/16 CHILLED LEAVING= 43.1~F; RETURN= 50.7~F EVAP = 35.8 PSIG; COND = 81.3 PSIG OIL PRESSURE = 38.2 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 72.7~F; RETURN = 65.1~F MOTOR CURRENT = 57 %FLA OPER. HOURS =44001; START COUNTER = 1991 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 40.7~F, COND= 76.6~F DISCHARGE TEMP=100.6~F,OIL TEMP=111.7~F HOP = 67.0 PSIG; LOP = 31.1 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON SUN 8:25AM SYSTEM CYCLING-AUTOSTART  HISTORY LOG 4 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS THU 6:04AM 11/10/16 CHILLED LEAVING= 44.2~F; RETURN= 52.5~F EVAP = 36.9 PSIG; COND = 89.0 PSIG OIL PRESSURE = 37.6 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 77.2~F; RETURN = 68.7~F MOTOR CURRENT = 64 %FLA OPER. HOURS =43944; START COUNTER = 1988 LEAVING SETPOINT = 44.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 41.8~F, COND= 81.3~F DISCHARGE TEMP=103.7~F,OIL TEMP=113.0~F HOP = 67.7 PSIG; LOP = 32.5 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON THU 6:04AM SYSTEM CYCLING-AUTOSTART