YORK SYSTEM 0 UPDATE c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS TUE 3:03PM 11/29/16 CHILLED LEAVING= 43.9~F; RETURN= 51.4~F EVAP = 36.4 PSIG; COND = 94.1 PSIG OIL PRESSURE = 38.0 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 80.4~F; RETURN = 74.3~F MOTOR CURRENT = 64 %FLA OPER. HOURS =44380; START COUNTER = 1995 LEAVING SETPOINT = 44.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 41.3~F, COND= 84.2~F DISCHARGE TEMP=106.0~F,OIL TEMP=115.5~F HOP = 67.7 PSIG; LOP = 32.2 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF TUEO 3 05PP