HISTORY LOG 1 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS MON 10:51AM 11/14/16 CHILLED LEAVING= 42.8~F; RETURN= 49.5~F EVAP = 34.4 PSIG; COND = 81.6 PSIG OIL PRESSURE = 41.5 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 74.2~F; RETURN = 68.7~F MOTOR CURRENT = 51 %FLA OPER. HOURS =46203; START COUNTER = 2084 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT=240MIN @ 99%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 39.2~F, COND= 76.7~F DISCHARGE TEMP=102.4~F,OIL TEMP=119.3~F HOP = 75.0 PSIG; LOP = 34.0 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON MON 10:51AM SYSTEM CYCLING-AUTOSTART  HISTORY LOG 2 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS MON 10:21AM 11/14/16 CHILLED LEAVING= 43.2~F; RETURN= 49.6~F EVAP = 39.0 PSIG; COND = 78.7 PSIG OIL PRESSURE = 22.0 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 73.8~F; RETURN = 68.5~F MOTOR CURRENT = 122 %FLA OPER. HOURS =46203; START COUNTER = 2083 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT=240MIN @ 99%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 42.5~F, COND= 76.6~F DISCHARGE TEMP=103.1~F,OIL TEMP=118.7~F HOP = 57.8 PSIG; LOP = 37.3 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - ON REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF MON 10:21AM LOW OIL PRESSURE  HISTORY LOG 3 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS THU 6:03PM 10/13/16 CHILLED LEAVING= 44.1~F; RETURN= 50.7~F EVAP = 38.3 PSIG; COND = 89.0 PSIG OIL PRESSURE = 42.3 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 77.7~F; RETURN = 72.4~F MOTOR CURRENT = 52 %FLA OPER. HOURS =45570; START COUNTER = 2076 LEAVING SETPOINT = 44.0~F CURRENT LIMIT= 95% FLA SETPOINT=240MIN @ 99%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 43.2~F, COND= 81.3~F DISCHARGE TEMP=105.7~F,OIL TEMP=123.3~F HOP = 77.2 PSIG; LOP = 36.6 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON SAT 6:37AM FLOW SWITCH-AUTOSTART  HISTORY LOG 4 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS MON 7:32PM 07/25/16 CHILLED LEAVING= 45.0~F; RETURN= 56.6~F EVAP = 61.0 PSIG; COND = 98.8 PSIG OIL PRESSURE = 46.4 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 93.7~F; RETURN = 84.7~F MOTOR CURRENT = 17 %FLA OPER. HOURS =44486; START COUNTER = 2032 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT=240MIN @ 99%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 62.7~F, COND= 86.9~F DISCHARGE TEMP=109.3~F,OIL TEMP=139.9~F HOP = 102.1 PSIG; LOP = 57.1 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF MON 10:12PM PWR FAULT-CALL YORK SERVICE