YORK SYSTEM 0 UPDATE c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS TUE 3:55PM 11/29/16 CHILLED LEAVING= 43.8~F; RETURN= 50.7~F EVAP = 37.9 PSIG; COND = 89.0 PSIG OIL PRESSURE = 41.8 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 77.7~F; RETURN = 71.4~F MOTOR CURRENT = 56 %FLA OPER. HOURS =46568; START COUNTER = 2085 LEAVING SETPOINT = 44.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 42.8~F, COND= 81.3~F DISCHARGE TEMP=105.5~F,OIL TEMP=123.0~F HOP = 76.9 PSIG; LOP = 35.8 PSIG SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF MONO10 53AP