HISTORY LOG 1 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS MON 7:26PM 07/25/16 CHILLED LEAVING= 45.4~F; RETURN= 56.7~F EVAP = 55.4 PSIG; COND = 84.6 PSIG OIL PRESSURE = 44.2 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 94.7~F; RETURN = 85.6~F MOTOR CURRENT = 19 %FLA OPER. HOURS =42834; START COUNTER = 1957 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 58.4~F, COND= 78.6~F DISCHARGE TEMP=116.9~F,OIL TEMP=133.1~F HOP = 93.7 PSIG; LOP = 50.9 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - CURRENT LIMIT IN EFFECT SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF MON 7:26PM PWR FAULT-CALL YORK SERVICE HISTORY LOG 2 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS SAT 5:09PM 07/09/16 CHILLED LEAVING= 46.9~F; RETURN= 57.1~F EVAP = 38.3 PSIG; COND = 103.6 PSIG OIL PRESSURE = 37.3 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 88.9~F; RETURN = 76.8~F MOTOR CURRENT = 97 %FLA OPER. HOURS =42628; START COUNTER = 1950 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 43.2~F, COND= 89.5~F DISCHARGE TEMP=113.2~F,OIL TEMP=123.3~F HOP = 71.0 PSIG; LOP = 35.1 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - CURRENT LIMIT IN EFFECT SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON SAT 5:09PM SYSTEM CYCLING-AUTOSTART HISTORY LOG 3 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS SAT 4:18PM 07/09/16 CHILLED LEAVING= 43.2~F; RETURN= 55.4~F EVAP = 32.0 PSIG; COND = 103.6 PSIG OIL PRESSURE = 37.7 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 91.3~F; RETURN = 82.4~F MOTOR CURRENT = 80 %FLA OPER. HOURS =42628; START COUNTER = 1949 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 36.6~F, COND= 89.5~F DISCHARGE TEMP=114.2~F,OIL TEMP=127.6~F HOP = 67.3 PSIG; LOP = 31.1 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON SAT 4:18PM FLOW SWITCH-AUTOSTART HISTORY LOG 4 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS THU 2:45PM 06/09/16 CHILLED LEAVING= 43.1~F; RETURN= 55.2~F EVAP = 34.6 PSIG; COND = 86.0 PSIG OIL PRESSURE = 38.5 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 79.6~F; RETURN = 68.2~F MOTOR CURRENT = 83 %FLA OPER. HOURS =42372; START COUNTER = 1937 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 39.4~F, COND= 79.5~F DISCHARGE TEMP=105.3~F,OIL TEMP=118.0~F HOP = 68.4 PSIG; LOP = 31.1 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON THU 2:45PM SYSTEM CYCLING-AUTOSTART