YORK SYSTEM 0 UPDATE c1992 YORK INTERNATIONAL CORP. VERSION C.03F.00 TODAY IS MON 7:26PM 07/25/16 CHILLED LEAVING= 45.4~F; RETURN= 56.7~F EVAP = 55.4 PSIG; COND = 84.6 PSIG OIL PRESSURE = 44.2 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 94.7~F; RETURN = 85.6~F MOTOR CURRENT = 19 %FLA OPER. HOURS =42834; START COUNTER = 1957 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 58.4~F, COND= 78.6~F DISCHARGE TEMP=116.9~F,OIL TEMP=133.1~F HOP = 93.7 PSIG; LOP = 50.9 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:00AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - CURRENT LIMIT IN EFFECT SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF MON 9:59PM PWR FAULT-CALL YORK SERVICE