HISTORY LOG 1 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.01 TODAY IS MON 7:59PM 07/25/16 CHILLED LEAVING= 45.7~F; RETURN= 57.1~F EVAP = 60.0 PSIG; COND = 93.4 PSIG OIL PRESSURE = 38.7 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 94.3~F; RETURN = 85.8~F MOTOR CURRENT = 20 %FLA OPER. HOURS =35358; START COUNTER = 1229 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 62.0~F, COND= 83.8~F DISCHARGE TEMP= 96.0~F,OIL TEMP=131.1~F HOP = 96.6 PSIG; LOP = 57.8 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:07AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO STRT=12:00AM INT= 1.1HRS 1.1HRS LFT SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON MON 7:59PM POWER FAULT-AUTOSTART HISTORY LOG 2 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.01 TODAY IS SUN 7:24PM 07/24/16 CHILLED LEAVING= 57.1~F; RETURN= 57.1~F EVAP = 53.3 PSIG; COND = 76.9 PSIG OIL PRESSURE = 33.7 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 82.2~F; RETURN = 82.2~F MOTOR CURRENT = %FLA OPER. HOURS =35335; START COUNTER = 1227 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 56.6~F, COND= 73.8~F DISCHARGE TEMP=109.3~F,OIL TEMP=131.1~F HOP = 65.1 PSIG; LOP = 31.8 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:07AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - OFF RETURN OIL SOLENOID VALVE - OFF OIL PUMP - ON CHILLED WATER PUMP - ON WTO STRT=12:00AM INT= 1.1HRS 1.1HRS LFT SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON SUN 7:24PM AC UNDERVOLTAGE-AUTOSTART HISTORY LOG 3 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.01 TODAY IS SUN 6:54PM 07/24/16 CHILLED LEAVING= 55.9~F; RETURN= 57.1~F EVAP = 49.3 PSIG; COND = 96.6 PSIG OIL PRESSURE = 31.9 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 84.0~F; RETURN = 82.0~F MOTOR CURRENT = %FLA OPER. HOURS =35335; START COUNTER = 1226 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 53.2~F, COND= 85.6~F DISCHARGE TEMP=107.2~F,OIL TEMP=131.2~F HOP = 72.5 PSIG; LOP = 40.6 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:07AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO STRT=12:00AM INT= 1.1HRS 1.1HRS LFT SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON SUN 6:54PM AC UNDERVOLTAGE-AUTOSTART HISTORY LOG 4 ;SYS 0 c1992 YORK INTERNATIONAL CORP. VERSION C.03F.01 TODAY IS THU 8:46AM 07/21/16 CHILLED LEAVING= 56.9~F; RETURN= 56.6~F EVAP = 54.1 PSIG; COND = 77.6 PSIG OIL PRESSURE = 32.5 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 75.5~F; RETURN = 75.1~F MOTOR CURRENT = %FLA OPER. HOURS =35318; START COUNTER = 1222 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 57.3~F, COND= 74.2~F DISCHARGE TEMP= 99.1~F,OIL TEMP=129.1~F HOP = 68.1 PSIG; LOP = 35.5 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:07AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - OFF RETURN OIL SOLENOID VALVE - OFF OIL PUMP - ON CHILLED WATER PUMP - ON WTO STRT=12:00AM INT= 1.1HRS 1.1HRS LFT SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON THU 8:46AM AC UNDERVOLTAGE-AUTOSTART