YORK SYSTEM 0 UPDATE c1992 YORK INTERNATIONAL CORP. VERSION C.03F.01 TODAY IS MON 10:57PM 07/25/16 CHILLED LEAVING= 42.4~F; RETURN= 54.2~F EVAP = 35.1 PSIG; COND = 104.0 PSIG OIL PRESSURE = 33.9 PSID NO OPTIONS INSTALLED SOLID STATE STARTER NOT INSTALLED COND LEAVING = 86.5~F; RETURN = 78.9~F MOTOR CURRENT = 76 %FLA OPER. HOURS =35361; START COUNTER = 1231 LEAVING SETPOINT = 43.0~F CURRENT LIMIT= 95% FLA SETPOINT= 0 MIN @ 100%FLA, 0 MIN LEFT S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20~F SAT TEMPS EVAP = 40.0~F, COND= 89.7~F DISCHARGE TEMP= 95.1~F,OIL TEMP=124.8~F HOP = 66.6 PSIG; LOP = 32.9 PSIG SUN START = 12:00AM, STOP = 12:00AM MON START = 12:00AM, STOP = 12:00AM TUE START = 12:00AM, STOP = 12:00AM WED START = 12:00AM, STOP = 12:00AM THU START = 12:00AM, STOP = 12:00AM FRI START = 12:00AM, STOP = 12:00AM SAT START = 12:00AM, STOP = 12:00AM HOL START = 12:00AM, STOP = 12:07AM COMP MOTOR STARTER - ON PRV CLOSE - OFF REMOTE MODE READY TO START RELAY - ON VENT LINE VALVE - ON RETURN OIL SOLENOID VALVE - ON OIL PUMP - ON CHILLED WATER PUMP - ON WTO STRT=12:00AM INT= 1.1HRS 1.1HRS LFT SYSTEM RUN - LEAVING TEMP CONTROL SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF MONO10 58PP