HISTORY LOG 1 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS TUE 11:16AM 05/24/16 CHILLED LEAVING= 45.0~F; RETURN= 51.0~F GEN PRESSURE = 251.8mmHgA;TEMP = 283.3~F REFRIGERANT = 44.1~F;SOLUTION = 172.6~F COND LEAVING = 86.8~F; RETURN = 79.4~F PURGE PUMP PRESSURE = 51.2mmHgA PURGE TANK PRESSURE = 54.8mmHgA OPER. HOURS =24147; START COUNTER = 779 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 48% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 66.4% 2ND STAGE LVG REFRIG TEMP = 160.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 2; TOTAL= 141 OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - PRESS STATUS WARNING - AUTO PURGE FAILURE WARNING - SOL'N CONCENTRATION OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC TUE 11:16AM-HIGH SOLUTION CONCENTRATION HISTORY LOG 2 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS THU 10:27AM 05/19/16 CHILLED LEAVING= 45.0~F; RETURN= 48.9~F GEN PRESSURE = 157.7mmHgA;TEMP = 257.3~F REFRIGERANT = 42.5~F;SOLUTION = 173.9~F COND LEAVING = 80.8~F; RETURN = 76.8~F PURGE PUMP PRESSURE = 44.0mmHgA PURGE TANK PRESSURE = 47.1mmHgA OPER. HOURS =24140; START COUNTER = 777 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 5% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 66.4% 2ND STAGE LVG REFRIG TEMP = 139.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 3; TOTAL= 141 OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - PRESS STATUS WARNING - SOL'N CONCENTRATION OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC THU 10:27AM-HIGH SOLUTION CONCENTRATION HISTORY LOG 3 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS THU 10:24AM 05/19/16 CHILLED LEAVING= 44.5~F; RETURN= 48.3~F GEN PRESSURE = 238.4mmHgA;TEMP = 259.3~F REFRIGERANT = 42.7~F;SOLUTION = 175.6~F COND LEAVING = 84.5~F; RETURN = 76.5~F PURGE PUMP PRESSURE = 44.0mmHgA PURGE TANK PRESSURE = 47.1mmHgA OPER. HOURS =24140; START COUNTER = 776 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 60% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 155.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 3; TOTAL= 141 OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - PRESS STATUS WARNING - SOL'N CONCENTRATION OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC THU 10:24AM COND FLOW SWITCH - AUTOSTART HISTORY LOG 4 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 4:03PM 09/30/15 CHILLED LEAVING= 44.1~F; RETURN= 52.0~F GEN PRESSURE = 280.3mmHgA;TEMP = 279.5~F REFRIGERANT = 40.3~F;SOLUTION = 175.1~F COND LEAVING = 84.0~F; RETURN = 72.4~F PURGE PUMP PRESSURE = 2.6mmHgA PURGE TANK PRESSURE = 32.6mmHgA OPER. HOURS =24117; START COUNTER = 774 LVG CHILLED WATER SETPOINT = 44.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 72% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 66.1% 2ND STAGE LVG REFRIG TEMP = 158.5~F REMOTE MODE READY TO START RELAY - ON CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 133 OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - PRESS STATUS REPLACE RTC, U16 - REPROGRAM SETPOINTS WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:14AM 05/18/16- P.F. DURATION = 0HR,10MIN, 3SEC WED 10:14AM SOLUTION PUMP OVERLOADS OPEN