c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS THU 1:58PM 05/08/08 CHILLED LEAVING= 44.7~F; RETURN= 55.1~F GEN PRESSURE = 475.2mmHgA;TEMP = 312.1~F REFRIGERANT = 40.0~F;SOLUTION = 175.9~F NO OPTIONS INSTALLED COND LEAVING = 88.9~F; RETURN = 77.2~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 48.6mmHgA OPER. HOURS =20399; START COUNTER = 476 LVG CHILLED WATER SETPOINT = 42.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 98% SETP=133MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 67.6% 2ND STAGE LVG REFRIG TEMP = 177.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 5; TOTAL= 1730 MAN PURGES LAST 7 DAYS= 1; TOTAL= 106 WTO STRT=12:00AM INT=13.3HRS 13.3HRS LFT SYSTEM RUN-LEAVING CHILLED WATER CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:28AM 05/05/08 P.F. DURATION = 0HR,41MIN, 6SEC