c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 9:24AM 05/14/08 CHILLED LEAVING= 51.3~F; RETURN= 50.4~F GEN PRESSURE = 522.3mmHgA;TEMP = 294.4~F REFRIGERANT = 52.5~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 74.8~F; RETURN = 72.7~F PURGE PUMP PRESSURE = 10.3mmHgA PURGE TANK PRESSURE = 29.0mmHgA OPER. HOURS =19060; START COUNTER = 512 LVG CHILLED WATER SETPOINT = 42.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.7% 2ND STAGE LVG REFRIG TEMP = 190.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 1578 MAN PURGES LAST 7 DAYS= 1; TOTAL= 168 OKI STRT= 5:27AM INT= .2HRS .2HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 5:09PM 05/13/08- P.F. DURATION = 0HR, 0MIN, 1SEC