YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:55PM 06/15/18 CHILLED LEAVING= 61.0~F; RETURN= 57.5~F GEN PRESSURE = 477.8mmHgA;TEMP = 288.9~F REFRIGERANT = 54.1~F;SOLUTION = 179.5~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 42.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 81% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.8% 2ND STAGE LVG REFRIG TEMP = 185.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:56PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.5~F GEN PRESSURE = 487.6mmHgA;TEMP = 289.9~F REFRIGERANT = 54.3~F;SOLUTION = 180.8~F NO OPTIONS INSTALLED COND LEAVING = 86.5~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 42.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 90% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.8% 2ND STAGE LVG REFRIG TEMP = 186.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:57PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.5~F GEN PRESSURE = 496.9mmHgA;TEMP = 290.6~F REFRIGERANT = 54.5~F;SOLUTION = 183.0~F NO OPTIONS INSTALLED COND LEAVING = 86.8~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 43.4mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 90% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 187.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:02PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.7~F GEN PRESSURE = 549.2mmHgA;TEMP = 292.7~F REFRIGERANT = 55.0~F;SOLUTION = 192.5~F NO OPTIONS INSTALLED COND LEAVING = 88.5~F; RETURN = 81.3~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 45.5mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.1% 2ND STAGE LVG REFRIG TEMP = 191.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:03PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.4~F GEN PRESSURE = 566.2mmHgA;TEMP = 293.7~F REFRIGERANT = 54.8~F;SOLUTION = 194.3~F NO OPTIONS INSTALLED COND LEAVING = 89.3~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 46.5mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 99% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.9% 2ND STAGE LVG REFRIG TEMP = 192.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:05PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.5~F GEN PRESSURE = 579.2mmHgA;TEMP = 294.8~F REFRIGERANT = 55.1~F;SOLUTION = 194.8~F NO OPTIONS INSTALLED COND LEAVING = 89.8~F; RETURN = 82.0~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 47.1mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.8% 2ND STAGE LVG REFRIG TEMP = 194.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:07PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 597.3mmHgA;TEMP = 297.9~F REFRIGERANT = 55.0~F;SOLUTION = 196.1~F NO OPTIONS INSTALLED COND LEAVING = 90.8~F; RETURN = 82.7~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 48.1mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.0% 2ND STAGE LVG REFRIG TEMP = 195.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:08PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.4~F GEN PRESSURE = 605.0mmHgA;TEMP = 299.0~F REFRIGERANT = 55.0~F;SOLUTION = 196.4~F NO OPTIONS INSTALLED COND LEAVING = 90.8~F; RETURN = 82.6~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 48.6mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.1% 2ND STAGE LVG REFRIG TEMP = 196.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:08PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.1~F GEN PRESSURE = 607.6mmHgA;TEMP = 299.4~F REFRIGERANT = 55.0~F;SOLUTION = 196.1~F NO OPTIONS INSTALLED COND LEAVING = 91.0~F; RETURN = 82.7~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 48.6mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.1% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:10PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 617.4mmHgA;TEMP = 301.3~F REFRIGERANT = 54.6~F;SOLUTION = 197.1~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 83.1~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 49.6mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 96% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 197.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT UNLOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:11PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 622.1mmHgA;TEMP = 302.0~F REFRIGERANT = 54.8~F;SOLUTION = 197.9~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 83.4~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 50.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 85% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 197.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT UNLOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:12PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 617.4mmHgA;TEMP = 303.2~F REFRIGERANT = 54.1~F;SOLUTION = 198.4~F NO OPTIONS INSTALLED COND LEAVING = 92.9~F; RETURN = 83.4~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 51.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 85% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 198.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:14PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.1~F GEN PRESSURE = 592.6mmHgA;TEMP = 304.7~F REFRIGERANT = 54.0~F;SOLUTION = 200.7~F NO OPTIONS INSTALLED COND LEAVING = 91.9~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 52.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 87% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.3% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:14PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.2~F GEN PRESSURE = 584.8mmHgA;TEMP = 306.6~F REFRIGERANT = 54.3~F;SOLUTION = 202.9~F NO OPTIONS INSTALLED COND LEAVING = 91.2~F; RETURN = 77.5~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 52.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 88% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 196.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:17PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.2~F GEN PRESSURE = 582.3mmHgA;TEMP = 309.3~F REFRIGERANT = 53.5~F;SOLUTION = 204.0~F NO OPTIONS INSTALLED COND LEAVING = 85.2~F; RETURN = 73.8~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 53.8mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 88% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 194.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:18PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.4~F GEN PRESSURE = 581.2mmHgA;TEMP = 309.7~F REFRIGERANT = 53.5~F;SOLUTION = 200.2~F NO OPTIONS INSTALLED COND LEAVING = 84.0~F; RETURN = 74.0~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 54.3mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 74% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 195.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT LOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:18PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.2~F GEN PRESSURE = 584.8mmHgA;TEMP = 309.7~F REFRIGERANT = 53.0~F;SOLUTION = 198.6~F NO OPTIONS INSTALLED COND LEAVING = 83.8~F; RETURN = 74.2~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 54.3mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 195.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:20PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 56.9~F GEN PRESSURE = 583.8mmHgA;TEMP = 310.5~F REFRIGERANT = 52.4~F;SOLUTION = 194.8~F NO OPTIONS INSTALLED COND LEAVING = 83.6~F; RETURN = 74.3~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 54.8mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 195.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:22PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 56.7~F GEN PRESSURE = 598.3mmHgA;TEMP = 311.3~F REFRIGERANT = 51.3~F;SOLUTION = 193.8~F NO OPTIONS INSTALLED COND LEAVING = 86.3~F; RETURN = 77.3~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 55.8mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 195.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:24PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 57.2~F GEN PRESSURE = 605.0mmHgA;TEMP = 310.5~F REFRIGERANT = 50.5~F;SOLUTION = 194.6~F NO OPTIONS INSTALLED COND LEAVING = 86.8~F; RETURN = 77.2~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 56.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:25PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 57.1~F GEN PRESSURE = 606.6mmHgA;TEMP = 310.5~F REFRIGERANT = 50.3~F;SOLUTION = 195.3~F NO OPTIONS INSTALLED COND LEAVING = 86.5~F; RETURN = 77.0~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:25PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 56.9~F GEN PRESSURE = 606.6mmHgA;TEMP = 310.5~F REFRIGERANT = 50.0~F;SOLUTION = 195.6~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 77.5~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:26PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 57.1~F GEN PRESSURE = 607.6mmHgA;TEMP = 310.9~F REFRIGERANT = 49.5~F;SOLUTION = 195.9~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 77.5~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:27PM 06/15/18 CHILLED LEAVING= 60.5~F; RETURN= 57.1~F GEN PRESSURE = 613.3mmHgA;TEMP = 311.3~F REFRIGERANT = 49.5~F;SOLUTION = 197.6~F NO OPTIONS INSTALLED COND LEAVING = 87.4~F; RETURN = 77.9~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 58.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 197.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:32PM 06/15/18 CHILLED LEAVING= 60.4~F; RETURN= 56.7~F GEN PRESSURE = 628.8mmHgA;TEMP = 314.2~F REFRIGERANT = 48.9~F;SOLUTION = 201.4~F NO OPTIONS INSTALLED COND LEAVING = 89.1~F; RETURN = 79.9~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 29.5mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.4% 2ND STAGE LVG REFRIG TEMP = 198.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:35PM 06/15/18 CHILLED LEAVING= 60.3~F; RETURN= 56.7~F GEN PRESSURE = 640.7mmHgA;TEMP = 316.8~F REFRIGERANT = 48.0~F;SOLUTION = 202.7~F NO OPTIONS INSTALLED COND LEAVING = 90.0~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 31.5mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 199.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:38PM 06/15/18 CHILLED LEAVING= 60.3~F; RETURN= 57.1~F GEN PRESSURE = 647.4mmHgA;TEMP = 317.2~F REFRIGERANT = 47.5~F;SOLUTION = 202.4~F NO OPTIONS INSTALLED COND LEAVING = 90.6~F; RETURN = 81.5~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 32.6mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 200.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:40PM 06/15/18 CHILLED LEAVING= 60.2~F; RETURN= 56.3~F GEN PRESSURE = 656.2mmHgA;TEMP = 318.4~F REFRIGERANT = 46.9~F;SOLUTION = 203.7~F NO OPTIONS INSTALLED COND LEAVING = 90.6~F; RETURN = 81.7~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 33.6mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 200.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:44PM 06/15/18 CHILLED LEAVING= 60.1~F; RETURN= 56.4~F GEN PRESSURE = 555.9mmHgA;TEMP = 319.3~F REFRIGERANT = 46.2~F;SOLUTION = 201.2~F NO OPTIONS INSTALLED COND LEAVING = 85.4~F; RETURN = 82.9~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 35.7mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.0% 2ND STAGE LVG REFRIG TEMP = 195.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:44PM 06/15/18 CHILLED LEAVING= 60.1~F; RETURN= 56.4~F GEN PRESSURE = 545.0mmHgA;TEMP = 318.8~F REFRIGERANT = 46.9~F;SOLUTION = 198.1~F NO OPTIONS INSTALLED COND LEAVING = 84.9~F; RETURN = 82.2~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 35.7mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.1% 2ND STAGE LVG REFRIG TEMP = 194.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:47PM 06/15/18 CHILLED LEAVING= 60.0~F; RETURN= 56.4~F GEN PRESSURE = 498.0mmHgA;TEMP = 308.9~F REFRIGERANT = 45.3~F;SOLUTION = 199.9~F NO OPTIONS INSTALLED COND LEAVING = 82.7~F; RETURN = 78.9~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 37.2mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 64.4% 2ND STAGE LVG REFRIG TEMP = 190.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:49PM 06/15/18 CHILLED LEAVING= 59.9~F; RETURN= 56.1~F GEN PRESSURE = 474.2mmHgA;TEMP = 302.0~F REFRIGERANT = 44.8~F;SOLUTION = 207.2~F NO OPTIONS INSTALLED COND LEAVING = 82.9~F; RETURN = 78.7~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 38.3mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 187.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:50PM 06/15/18 CHILLED LEAVING= 59.9~F; RETURN= 56.1~F GEN PRESSURE = 471.6mmHgA;TEMP = 297.9~F REFRIGERANT = 45.0~F;SOLUTION = 207.7~F NO OPTIONS INSTALLED COND LEAVING = 82.0~F; RETURN = 78.4~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 38.8mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 186.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:56PM 06/15/18 CHILLED LEAVING= 51.3~F; RETURN= 54.8~F GEN PRESSURE = 420.4mmHgA;TEMP = 281.1~F REFRIGERANT = 43.8~F;SOLUTION = 194.6~F NO OPTIONS INSTALLED COND LEAVING = 82.9~F; RETURN = 79.6~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 41.4mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.0% 2ND STAGE LVG REFRIG TEMP = 181.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:57PM 06/15/18 CHILLED LEAVING= 47.9~F; RETURN= 49.9~F GEN PRESSURE = 415.2mmHgA;TEMP = 279.2~F REFRIGERANT = 43.7~F;SOLUTION = 194.0~F NO OPTIONS INSTALLED COND LEAVING = 82.7~F; RETURN = 79.2~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 41.9mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.8% 2ND STAGE LVG REFRIG TEMP = 180.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:00PM 06/15/18 CHILLED LEAVING= 50.5~F; RETURN= 52.4~F GEN PRESSURE = 392.0mmHgA;TEMP = 275.7~F REFRIGERANT = 45.0~F;SOLUTION = 193.8~F NO OPTIONS INSTALLED COND LEAVING = 83.6~F; RETURN = 79.6~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 43.4mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.6% 2ND STAGE LVG REFRIG TEMP = 178.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:02PM 06/15/18 CHILLED LEAVING= 51.1~F; RETURN= 52.7~F GEN PRESSURE = 369.2mmHgA;TEMP = 274.8~F REFRIGERANT = 46.3~F;SOLUTION = 193.8~F NO OPTIONS INSTALLED COND LEAVING = 83.6~F; RETURN = 79.9~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 44.0mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.8% 2ND STAGE LVG REFRIG TEMP = 176.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:05PM 06/15/18 CHILLED LEAVING= 51.7~F; RETURN= 52.7~F GEN PRESSURE = 287.5mmHgA;TEMP = 265.0~F REFRIGERANT = 49.1~F;SOLUTION = 185.7~F NO OPTIONS INSTALLED COND LEAVING = 82.7~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 45.5mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.0% 2ND STAGE LVG REFRIG TEMP = 167.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:07PM 06/15/18 CHILLED LEAVING= 52.0~F; RETURN= 52.7~F GEN PRESSURE = 246.7mmHgA;TEMP = 255.9~F REFRIGERANT = 50.3~F;SOLUTION = 188.1~F NO OPTIONS INSTALLED COND LEAVING = 83.1~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 46.5mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 53% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.8% 2ND STAGE LVG REFRIG TEMP = 160.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:11PM 06/15/18 CHILLED LEAVING= 52.1~F; RETURN= 52.8~F GEN PRESSURE = 298.9mmHgA;TEMP = 243.4~F REFRIGERANT = 51.1~F;SOLUTION = 190.9~F NO OPTIONS INSTALLED COND LEAVING = 83.1~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 60.0mmHgA PURGE TANK PRESSURE = 47.6mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 65% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 58.7% 2ND STAGE LVG REFRIG TEMP = 157.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:14PM 06/15/18 CHILLED LEAVING= 52.4~F; RETURN= 53.0~F GEN PRESSURE = 374.9mmHgA;TEMP = 251.7~F REFRIGERANT = 51.9~F;SOLUTION = 191.7~F NO OPTIONS INSTALLED COND LEAVING = 84.9~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 49.1mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 99% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 56.6% 2ND STAGE LVG REFRIG TEMP = 173.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT LOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:17PM 06/15/18 CHILLED LEAVING= 51.6~F; RETURN= 53.1~F GEN PRESSURE = 424.0mmHgA;TEMP = 268.5~F REFRIGERANT = 52.2~F;SOLUTION = 183.8~F NO OPTIONS INSTALLED COND LEAVING = 86.1~F; RETURN = 77.9~F PURGE PUMP PRESSURE = 60.0mmHgA PURGE TANK PRESSURE = 50.7mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 59.2% 2ND STAGE LVG REFRIG TEMP = 178.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:17PM 06/15/18 CHILLED LEAVING= 51.3~F; RETURN= 52.8~F GEN PRESSURE = 439.0mmHgA;TEMP = 271.2~F REFRIGERANT = 52.2~F;SOLUTION = 182.4~F NO OPTIONS INSTALLED COND LEAVING = 87.2~F; RETURN = 78.4~F PURGE PUMP PRESSURE = 60.0mmHgA PURGE TANK PRESSURE = 51.2mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 59.2% 2ND STAGE LVG REFRIG TEMP = 180.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:20PM 06/15/18 CHILLED LEAVING= 51.0~F; RETURN= 52.7~F GEN PRESSURE = 491.2mmHgA;TEMP = 276.3~F REFRIGERANT = 51.9~F;SOLUTION = 182.2~F NO OPTIONS INSTALLED COND LEAVING = 90.6~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 52.2mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 59.2% 2ND STAGE LVG REFRIG TEMP = 185.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:21PM 06/15/18 CHILLED LEAVING= 50.7~F; RETURN= 52.8~F GEN PRESSURE = 514.0mmHgA;TEMP = 281.8~F REFRIGERANT = 51.9~F;SOLUTION = 183.5~F NO OPTIONS INSTALLED COND LEAVING = 91.2~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 60.0mmHgA PURGE TANK PRESSURE = 52.7mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 59.7% 2ND STAGE LVG REFRIG TEMP = 187.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:23PM 06/15/18 CHILLED LEAVING= 50.4~F; RETURN= 53.0~F GEN PRESSURE = 561.6mmHgA;TEMP = 291.7~F REFRIGERANT = 51.7~F;SOLUTION = 187.3~F NO OPTIONS INSTALLED COND LEAVING = 91.3~F; RETURN = 79.7~F PURGE PUMP PRESSURE = 60.0mmHgA PURGE TANK PRESSURE = 53.8mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.9% 2ND STAGE LVG REFRIG TEMP = 191.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:26PM 06/15/18 CHILLED LEAVING= 49.8~F; RETURN= 52.4~F GEN PRESSURE = 604.0mmHgA;TEMP = 292.0~F REFRIGERANT = 51.4~F;SOLUTION = 185.4~F NO OPTIONS INSTALLED COND LEAVING = 92.1~F; RETURN = 81.3~F PURGE PUMP PRESSURE = 197.0mmHgA PURGE TANK PRESSURE = 54.8mmHgA OPER. HOURS =28111; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.0% 2ND STAGE LVG REFRIG TEMP = 195.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - 2SOL FAIL;MANUAL CLOSE VP2,VP5 WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:29PM 06/15/18 CHILLED LEAVING= 49.3~F; RETURN= 52.4~F GEN PRESSURE = 630.3mmHgA;TEMP = 294.1~F REFRIGERANT = 50.6~F;SOLUTION = 187.0~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 188.2mmHgA PURGE TANK PRESSURE = 56.4mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 59.5% 2ND STAGE LVG REFRIG TEMP = 198.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT UNLOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:32PM 06/15/18 CHILLED LEAVING= 48.5~F; RETURN= 52.0~F GEN PRESSURE = 626.7mmHgA;TEMP = 296.1~F REFRIGERANT = 50.5~F;SOLUTION = 190.9~F NO OPTIONS INSTALLED COND LEAVING = 89.1~F; RETURN = 78.9~F PURGE PUMP PRESSURE = 120.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 60.0% 2ND STAGE LVG REFRIG TEMP = 198.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:35PM 06/15/18 CHILLED LEAVING= 48.6~F; RETURN= 52.2~F GEN PRESSURE = 641.7mmHgA;TEMP = 300.1~F REFRIGERANT = 49.9~F;SOLUTION = 195.9~F NO OPTIONS INSTALLED COND LEAVING = 91.0~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 120.5mmHgA PURGE TANK PRESSURE = 59.5mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 69% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 60.7% 2ND STAGE LVG REFRIG TEMP = 199.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:36PM 06/15/18 CHILLED LEAVING= 48.6~F; RETURN= 52.0~F GEN PRESSURE = 623.1mmHgA;TEMP = 303.2~F REFRIGERANT = 49.5~F;SOLUTION = 197.9~F NO OPTIONS INSTALLED COND LEAVING = 90.8~F; RETURN = 81.5~F PURGE PUMP PRESSURE = 120.5mmHgA PURGE TANK PRESSURE = 60.5mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 59% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.4% 2ND STAGE LVG REFRIG TEMP = 199.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:38PM 06/15/18 CHILLED LEAVING= 48.4~F; RETURN= 52.2~F GEN PRESSURE = 604.0mmHgA;TEMP = 305.9~F REFRIGERANT = 49.7~F;SOLUTION = 198.1~F NO OPTIONS INSTALLED COND LEAVING = 88.5~F; RETURN = 80.1~F PURGE PUMP PRESSURE > 219.8mmHgA PURGE TANK PRESSURE = 61.0mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 59% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 62.0% 2ND STAGE LVG REFRIG TEMP = 197.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:44PM 06/15/18 CHILLED LEAVING= 48.2~F; RETURN= 52.2~F GEN PRESSURE = 567.3mmHgA;TEMP = 302.8~F REFRIGERANT = 49.1~F;SOLUTION = 201.4~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 79.7~F PURGE PUMP PRESSURE > 219.8mmHgA PURGE TANK PRESSURE = 64.1mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.3% 2ND STAGE LVG REFRIG TEMP = 194.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:46PM 06/15/18 CHILLED LEAVING= 48.2~F; RETURN= 52.2~F GEN PRESSURE = 560.5mmHgA;TEMP = 300.9~F REFRIGERANT = 48.9~F;SOLUTION = 197.1~F NO OPTIONS INSTALLED COND LEAVING = 86.1~F; RETURN = 78.9~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 65.7mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 66% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.1% 2ND STAGE LVG REFRIG TEMP = 193.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:50PM 06/15/18 CHILLED LEAVING= 48.2~F; RETURN= 52.2~F GEN PRESSURE = 617.4mmHgA;TEMP = 306.6~F REFRIGERANT = 48.9~F;SOLUTION = 207.5~F NO OPTIONS INSTALLED COND LEAVING = 90.2~F; RETURN = 80.6~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 66.7mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 63% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 62.4% 2ND STAGE LVG REFRIG TEMP = 197.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:54PM 06/15/18 CHILLED LEAVING= 48.5~F; RETURN= 52.4~F GEN PRESSURE = 577.6mmHgA;TEMP = 312.6~F REFRIGERANT = 48.6~F;SOLUTION = 205.0~F NO OPTIONS INSTALLED COND LEAVING = 88.2~F; RETURN = 80.6~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 68.8mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 199.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC FRI 3:54PM SOLUTION PUMP OVERLOADS OPEN YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:54PM 06/15/18 CHILLED LEAVING= 48.5~F; RETURN= 52.7~F GEN PRESSURE = 570.9mmHgA;TEMP = 313.0~F REFRIGERANT = 48.9~F;SOLUTION = 205.0~F NO OPTIONS INSTALLED COND LEAVING = 88.0~F; RETURN = 80.4~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 68.8mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 199.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC FRI 3:54PM SOLUTION PUMP OVERLOADS OPEN YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:01PM 06/15/18 CHILLED LEAVING= 52.9~F; RETURN= 53.1~F GEN PRESSURE = 262.2mmHgA;TEMP = 277.0~F REFRIGERANT = 49.2~F;SOLUTION = 254.2~F NO OPTIONS INSTALLED COND LEAVING = 81.8~F; RETURN = 79.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 69.3mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 0% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 65.7% 2ND STAGE LVG REFRIG TEMP = 158.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - OFF PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT LOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:02PM 06/15/18 CHILLED LEAVING= 52.9~F; RETURN= 53.0~F GEN PRESSURE = 280.8mmHgA;TEMP = 273.0~F REFRIGERANT = 49.2~F;SOLUTION = 227.0~F NO OPTIONS INSTALLED COND LEAVING = 81.0~F; RETURN = 79.4~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 69.8mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 55% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 64.7% 2ND STAGE LVG REFRIG TEMP = 158.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT LOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:02PM 06/15/18 CHILLED LEAVING= 53.0~F; RETURN= 53.6~F GEN PRESSURE = 311.3mmHgA;TEMP = 270.9~F REFRIGERANT = 49.2~F;SOLUTION = 212.0~F NO OPTIONS INSTALLED COND LEAVING = 80.4~F; RETURN = 79.4~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 69.8mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 55% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 161.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:04PM 06/15/18 CHILLED LEAVING= 53.2~F; RETURN= 53.3~F GEN PRESSURE = 387.3mmHgA;TEMP = 265.8~F REFRIGERANT = 50.3~F;SOLUTION = 171.7~F NO OPTIONS INSTALLED COND LEAVING = 81.0~F; RETURN = 79.2~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 71.4mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 59.7% 2ND STAGE LVG REFRIG TEMP = 174.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT LOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:05PM 06/15/18 CHILLED LEAVING= 53.2~F; RETURN= 53.1~F GEN PRESSURE = 486.6mmHgA;TEMP = 269.7~F REFRIGERANT = 50.8~F;SOLUTION = 170.3~F NO OPTIONS INSTALLED COND LEAVING = 84.5~F; RETURN = 78.9~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 71.9mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 64% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 59.3% 2ND STAGE LVG REFRIG TEMP = 179.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:08PM 06/15/18 CHILLED LEAVING= 53.4~F; RETURN= 53.4~F GEN PRESSURE = 499.5mmHgA;TEMP = 286.2~F REFRIGERANT = 52.0~F;SOLUTION = 178.7~F NO OPTIONS INSTALLED COND LEAVING = 81.5~F; RETURN = 79.2~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 72.9mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 54% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 60.4% 2ND STAGE LVG REFRIG TEMP = 188.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:13PM 06/15/18 CHILLED LEAVING= 53.3~F; RETURN= 53.3~F GEN PRESSURE = 530.0mmHgA;TEMP = 292.7~F REFRIGERANT = 53.5~F;SOLUTION = 190.7~F NO OPTIONS INSTALLED COND LEAVING = 81.5~F; RETURN = 78.5~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 75.5mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 54% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.2% 2ND STAGE LVG REFRIG TEMP = 190.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:14PM 06/15/18 CHILLED LEAVING= 53.4~F; RETURN= 53.6~F GEN PRESSURE = 531.1mmHgA;TEMP = 293.4~F REFRIGERANT = 53.2~F;SOLUTION = 192.0~F NO OPTIONS INSTALLED COND LEAVING = 81.8~F; RETURN = 78.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 75.5mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 54% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.2% 2ND STAGE LVG REFRIG TEMP = 191.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:16PM 06/15/18 CHILLED LEAVING= 53.2~F; RETURN= 53.3~F GEN PRESSURE = 579.2mmHgA;TEMP = 294.4~F REFRIGERANT = 53.8~F;SOLUTION = 194.8~F NO OPTIONS INSTALLED COND LEAVING = 82.6~F; RETURN = 78.2~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 76.5mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 65% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 191.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:20PM 06/15/18 CHILLED LEAVING= 53.3~F; RETURN= 53.6~F GEN PRESSURE = 636.0mmHgA;TEMP = 308.1~F REFRIGERANT = 53.8~F;SOLUTION = 205.2~F NO OPTIONS INSTALLED COND LEAVING = 85.8~F; RETURN = 79.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 78.1mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 64% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.2% 2ND STAGE LVG REFRIG TEMP = 199.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:26PM 06/15/18 CHILLED LEAVING= 53.1~F; RETURN= 53.3~F GEN PRESSURE = 589.0mmHgA;TEMP = 315.1~F REFRIGERANT = 53.5~F;SOLUTION = 201.2~F NO OPTIONS INSTALLED COND LEAVING = 84.3~F; RETURN = 81.1~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 81.2mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 63.4% 2ND STAGE LVG REFRIG TEMP = 199.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:29PM 06/15/18 CHILLED LEAVING= 52.9~F; RETURN= 53.1~F GEN PRESSURE = 528.0mmHgA;TEMP = 306.6~F REFRIGERANT = 54.0~F;SOLUTION = 185.7~F NO OPTIONS INSTALLED COND LEAVING = 84.2~F; RETURN = 81.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 82.7mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 192.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:32PM 06/15/18 CHILLED LEAVING= 52.8~F; RETURN= 53.4~F GEN PRESSURE = 500.6mmHgA;TEMP = 296.1~F REFRIGERANT = 53.3~F;SOLUTION = 193.8~F NO OPTIONS INSTALLED COND LEAVING = 83.3~F; RETURN = 80.6~F PURGE PUMP PRESSURE > 219.8mmHgA PURGE TANK PRESSURE = 84.3mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.2% 2ND STAGE LVG REFRIG TEMP = 188.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:33PM 06/15/18 CHILLED LEAVING= 52.7~F; RETURN= 53.4~F GEN PRESSURE = 494.9mmHgA;TEMP = 294.1~F REFRIGERANT = 54.0~F;SOLUTION = 196.4~F NO OPTIONS INSTALLED COND LEAVING = 82.7~F; RETURN = 79.9~F PURGE PUMP PRESSURE > 219.8mmHgA PURGE TANK PRESSURE = 84.8mmHgA OPER. HOURS =28112; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.8% 2ND STAGE LVG REFRIG TEMP = 188.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:38PM 06/15/18 CHILLED LEAVING= 52.2~F; RETURN= 52.8~F GEN PRESSURE = 478.8mmHgA;TEMP = 288.9~F REFRIGERANT = 53.5~F;SOLUTION = 202.2~F NO OPTIONS INSTALLED COND LEAVING = 82.0~F; RETURN = 79.4~F PURGE PUMP PRESSURE = 9.8mmHgA PURGE TANK PRESSURE = 87.4mmHgA OPER. HOURS =28113; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 186.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:42PM 06/15/18 CHILLED LEAVING= 51.7~F; RETURN= 53.3~F GEN PRESSURE = 461.8mmHgA;TEMP = 287.9~F REFRIGERANT = 53.0~F;SOLUTION = 200.2~F NO OPTIONS INSTALLED COND LEAVING = 81.8~F; RETURN = 79.1~F PURGE PUMP PRESSURE = 10.3mmHgA PURGE TANK PRESSURE = 30.0mmHgA OPER. HOURS =28113; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 185.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:44PM 06/15/18 CHILLED LEAVING= 51.6~F; RETURN= 53.0~F GEN PRESSURE = 453.5mmHgA;TEMP = 288.2~F REFRIGERANT = 53.0~F;SOLUTION = 200.4~F NO OPTIONS INSTALLED COND LEAVING = 82.6~F; RETURN = 79.7~F PURGE PUMP PRESSURE = 9.8mmHgA PURGE TANK PRESSURE = 30.5mmHgA OPER. HOURS =28113; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.7% 2ND STAGE LVG REFRIG TEMP = 184.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:50PM 06/15/18 CHILLED LEAVING= 50.8~F; RETURN= 52.7~F GEN PRESSURE = 379.6mmHgA;TEMP = 287.9~F REFRIGERANT = 52.2~F;SOLUTION = 207.0~F NO OPTIONS INSTALLED COND LEAVING = 83.1~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 4.7mmHgA PURGE TANK PRESSURE = 32.6mmHgA OPER. HOURS =28113; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 177.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:52PM 06/15/18 CHILLED LEAVING= 50.8~F; RETURN= 52.7~F GEN PRESSURE = 352.1mmHgA;TEMP = 282.7~F REFRIGERANT = 51.9~F;SOLUTION = 205.2~F NO OPTIONS INSTALLED COND LEAVING = 83.4~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 4.1mmHgA PURGE TANK PRESSURE = 33.1mmHgA OPER. HOURS =28113; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 63.1% 2ND STAGE LVG REFRIG TEMP = 174.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:53PM 06/15/18 CHILLED LEAVING= 50.9~F; RETURN= 52.7~F GEN PRESSURE = 344.4mmHgA;TEMP = 280.2~F REFRIGERANT = 51.9~F;SOLUTION = 205.0~F NO OPTIONS INSTALLED COND LEAVING = 83.8~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 3.6mmHgA PURGE TANK PRESSURE = 33.6mmHgA OPER. HOURS =28113; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 173.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:53PM 06/15/18 CHILLED LEAVING= 50.9~F; RETURN= 52.7~F GEN PRESSURE = 344.4mmHgA;TEMP = 280.2~F REFRIGERANT = 51.9~F;SOLUTION = 205.0~F NO OPTIONS INSTALLED COND LEAVING = 83.8~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 3.6mmHgA PURGE TANK PRESSURE = 33.6mmHgA OPER. HOURS =28113; START COUNTER = 806 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 173.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:56PM 06/15/18 CHILLED LEAVING= 50.7~F; RETURN= 52.7~F GEN PRESSURE = 253.4mmHgA;TEMP = 272.7~F REFRIGERANT = 51.7~F;SOLUTION = 199.9~F NO OPTIONS INSTALLED COND LEAVING = 82.9~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 3.1mmHgA PURGE TANK PRESSURE = 34.1mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 0% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 163.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:58PM 06/15/18 CHILLED LEAVING= 51.0~F; RETURN= 52.7~F GEN PRESSURE = 213.6mmHgA;TEMP = 259.8~F REFRIGERANT = 51.4~F;SOLUTION = 201.9~F NO OPTIONS INSTALLED COND LEAVING = 81.8~F; RETURN = 79.7~F PURGE PUMP PRESSURE = 3.1mmHgA PURGE TANK PRESSURE = 35.2mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 25% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 154.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 4:59PM 06/15/18 CHILLED LEAVING= 51.1~F; RETURN= 52.7~F GEN PRESSURE = 253.4mmHgA;TEMP = 257.0~F REFRIGERANT = 51.4~F;SOLUTION = 202.2~F NO OPTIONS INSTALLED COND LEAVING = 81.7~F; RETURN = 79.7~F PURGE PUMP PRESSURE = 3.1mmHgA PURGE TANK PRESSURE = 35.2mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 65% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 153.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:02PM 06/15/18 CHILLED LEAVING= 51.4~F; RETURN= 52.2~F GEN PRESSURE = 418.3mmHgA;TEMP = 257.9~F REFRIGERANT = 51.6~F;SOLUTION = 198.1~F NO OPTIONS INSTALLED COND LEAVING = 81.3~F; RETURN = 79.2~F PURGE PUMP PRESSURE = 2.6mmHgA PURGE TANK PRESSURE = 36.2mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 64% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 57.5% 2ND STAGE LVG REFRIG TEMP = 175.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:08PM 06/15/18 CHILLED LEAVING= 51.3~F; RETURN= 52.8~F GEN PRESSURE = 527.4mmHgA;TEMP = 276.7~F REFRIGERANT = 51.7~F;SOLUTION = 192.0~F NO OPTIONS INSTALLED COND LEAVING = 84.5~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 38.3mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 60% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 58.1% 2ND STAGE LVG REFRIG TEMP = 189.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:13PM 06/15/18 CHILLED LEAVING= 51.2~F; RETURN= 53.1~F GEN PRESSURE = 591.6mmHgA;TEMP = 291.3~F REFRIGERANT = 51.9~F;SOLUTION = 197.1~F NO OPTIONS INSTALLED COND LEAVING = 86.5~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 40.9mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 64% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 59.9% 2ND STAGE LVG REFRIG TEMP = 195.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:14PM 06/15/18 CHILLED LEAVING= 51.2~F; RETURN= 53.1~F GEN PRESSURE = 595.2mmHgA;TEMP = 292.0~F REFRIGERANT = 51.9~F;SOLUTION = 198.1~F NO OPTIONS INSTALLED COND LEAVING = 87.4~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 40.9mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 64% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 60.0% 2ND STAGE LVG REFRIG TEMP = 195.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:16PM 06/15/18 CHILLED LEAVING= 50.9~F; RETURN= 53.4~F GEN PRESSURE = 577.6mmHgA;TEMP = 294.4~F REFRIGERANT = 51.7~F;SOLUTION = 200.4~F NO OPTIONS INSTALLED COND LEAVING = 85.9~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 41.9mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 60.3% 2ND STAGE LVG REFRIG TEMP = 196.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:20PM 06/15/18 CHILLED LEAVING= 50.8~F; RETURN= 53.0~F GEN PRESSURE = 578.1mmHgA;TEMP = 295.8~F REFRIGERANT = 51.4~F;SOLUTION = 200.4~F NO OPTIONS INSTALLED COND LEAVING = 87.0~F; RETURN = 82.2~F PURGE PUMP PRESSURE = 3.6mmHgA PURGE TANK PRESSURE = 28.4mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 60.8% 2ND STAGE LVG REFRIG TEMP = 194.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:21PM 06/15/18 CHILLED LEAVING= 50.8~F; RETURN= 53.0~F GEN PRESSURE = 580.2mmHgA;TEMP = 295.4~F REFRIGERANT = 51.6~F;SOLUTION = 201.4~F NO OPTIONS INSTALLED COND LEAVING = 87.8~F; RETURN = 83.3~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 29.5mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 60.7% 2ND STAGE LVG REFRIG TEMP = 194.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:26PM 06/15/18 CHILLED LEAVING= 50.7~F; RETURN= 53.1~F GEN PRESSURE = 589.5mmHgA;TEMP = 297.5~F REFRIGERANT = 51.3~F;SOLUTION = 205.0~F NO OPTIONS INSTALLED COND LEAVING = 88.7~F; RETURN = 83.6~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 31.5mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 60.8% 2ND STAGE LVG REFRIG TEMP = 196.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:32PM 06/15/18 CHILLED LEAVING= 50.5~F; RETURN= 53.3~F GEN PRESSURE = 604.0mmHgA;TEMP = 300.5~F REFRIGERANT = 51.3~F;SOLUTION = 207.0~F NO OPTIONS INSTALLED COND LEAVING = 89.8~F; RETURN = 84.9~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 34.1mmHgA OPER. HOURS =28113; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.1% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:38PM 06/15/18 CHILLED LEAVING= 50.1~F; RETURN= 53.3~F GEN PRESSURE = 596.2mmHgA;TEMP = 302.0~F REFRIGERANT = 51.3~F;SOLUTION = 208.7~F NO OPTIONS INSTALLED COND LEAVING = 87.8~F; RETURN = 81.8~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 37.2mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.7% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:41PM 06/15/18 CHILLED LEAVING= 49.8~F; RETURN= 53.6~F GEN PRESSURE = 589.0mmHgA;TEMP = 303.2~F REFRIGERANT = 50.9~F;SOLUTION = 208.7~F NO OPTIONS INSTALLED COND LEAVING = 87.8~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 38.8mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 62.0% 2ND STAGE LVG REFRIG TEMP = 196.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:44PM 06/15/18 CHILLED LEAVING= 49.4~F; RETURN= 53.6~F GEN PRESSURE = 578.1mmHgA;TEMP = 303.6~F REFRIGERANT = 50.5~F;SOLUTION = 206.2~F NO OPTIONS INSTALLED COND LEAVING = 85.9~F; RETURN = 79.7~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 40.3mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 62.2% 2ND STAGE LVG REFRIG TEMP = 195.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:47PM 06/15/18 CHILLED LEAVING= 49.2~F; RETURN= 53.7~F GEN PRESSURE = 571.9mmHgA;TEMP = 302.0~F REFRIGERANT = 50.3~F;SOLUTION = 204.7~F NO OPTIONS INSTALLED COND LEAVING = 85.9~F; RETURN = 79.7~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 41.9mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 62.1% 2ND STAGE LVG REFRIG TEMP = 194.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC