YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:55PM 06/15/18 CHILLED LEAVING= 61.0~F; RETURN= 57.5~F GEN PRESSURE = 477.8mmHgA;TEMP = 288.9~F REFRIGERANT = 54.1~F;SOLUTION = 179.5~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 42.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 81% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.8% 2ND STAGE LVG REFRIG TEMP = 185.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:56PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.5~F GEN PRESSURE = 487.6mmHgA;TEMP = 289.9~F REFRIGERANT = 54.3~F;SOLUTION = 180.8~F NO OPTIONS INSTALLED COND LEAVING = 86.5~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 42.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 90% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.8% 2ND STAGE LVG REFRIG TEMP = 186.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:57PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.5~F GEN PRESSURE = 496.9mmHgA;TEMP = 290.6~F REFRIGERANT = 54.5~F;SOLUTION = 183.0~F NO OPTIONS INSTALLED COND LEAVING = 86.8~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 43.4mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 90% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 187.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:02PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.7~F GEN PRESSURE = 549.2mmHgA;TEMP = 292.7~F REFRIGERANT = 55.0~F;SOLUTION = 192.5~F NO OPTIONS INSTALLED COND LEAVING = 88.5~F; RETURN = 81.3~F PURGE PUMP PRESSURE = 60.5mmHgA PURGE TANK PRESSURE = 45.5mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.1% 2ND STAGE LVG REFRIG TEMP = 191.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:03PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.4~F GEN PRESSURE = 566.2mmHgA;TEMP = 293.7~F REFRIGERANT = 54.8~F;SOLUTION = 194.3~F NO OPTIONS INSTALLED COND LEAVING = 89.3~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 46.5mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 99% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.9% 2ND STAGE LVG REFRIG TEMP = 192.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:05PM 06/15/18 CHILLED LEAVING= 60.9~F; RETURN= 57.5~F GEN PRESSURE = 579.2mmHgA;TEMP = 294.8~F REFRIGERANT = 55.1~F;SOLUTION = 194.8~F NO OPTIONS INSTALLED COND LEAVING = 89.8~F; RETURN = 82.0~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 47.1mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 60.8% 2ND STAGE LVG REFRIG TEMP = 194.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:07PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 597.3mmHgA;TEMP = 297.9~F REFRIGERANT = 55.0~F;SOLUTION = 196.1~F NO OPTIONS INSTALLED COND LEAVING = 90.8~F; RETURN = 82.7~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 48.1mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.0% 2ND STAGE LVG REFRIG TEMP = 195.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:08PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.4~F GEN PRESSURE = 605.0mmHgA;TEMP = 299.0~F REFRIGERANT = 55.0~F;SOLUTION = 196.4~F NO OPTIONS INSTALLED COND LEAVING = 90.8~F; RETURN = 82.6~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 48.6mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.1% 2ND STAGE LVG REFRIG TEMP = 196.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:08PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.1~F GEN PRESSURE = 607.6mmHgA;TEMP = 299.4~F REFRIGERANT = 55.0~F;SOLUTION = 196.1~F NO OPTIONS INSTALLED COND LEAVING = 91.0~F; RETURN = 82.7~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 48.6mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.1% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:10PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 617.4mmHgA;TEMP = 301.3~F REFRIGERANT = 54.6~F;SOLUTION = 197.1~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 83.1~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 49.6mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 96% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 197.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT UNLOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:11PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 622.1mmHgA;TEMP = 302.0~F REFRIGERANT = 54.8~F;SOLUTION = 197.9~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 83.4~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 50.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 85% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 197.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT UNLOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:12PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.2~F GEN PRESSURE = 617.4mmHgA;TEMP = 303.2~F REFRIGERANT = 54.1~F;SOLUTION = 198.4~F NO OPTIONS INSTALLED COND LEAVING = 92.9~F; RETURN = 83.4~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 51.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 85% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 198.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:14PM 06/15/18 CHILLED LEAVING= 60.8~F; RETURN= 57.1~F GEN PRESSURE = 592.6mmHgA;TEMP = 304.7~F REFRIGERANT = 54.0~F;SOLUTION = 200.7~F NO OPTIONS INSTALLED COND LEAVING = 91.9~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 52.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 87% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.3% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:14PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.2~F GEN PRESSURE = 584.8mmHgA;TEMP = 306.6~F REFRIGERANT = 54.3~F;SOLUTION = 202.9~F NO OPTIONS INSTALLED COND LEAVING = 91.2~F; RETURN = 77.5~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 52.2mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 88% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 196.0~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:17PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.2~F GEN PRESSURE = 582.3mmHgA;TEMP = 309.3~F REFRIGERANT = 53.5~F;SOLUTION = 204.0~F NO OPTIONS INSTALLED COND LEAVING = 85.2~F; RETURN = 73.8~F PURGE PUMP PRESSURE = 61.0mmHgA PURGE TANK PRESSURE = 53.8mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 88% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 194.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:18PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.4~F GEN PRESSURE = 581.2mmHgA;TEMP = 309.7~F REFRIGERANT = 53.5~F;SOLUTION = 200.2~F NO OPTIONS INSTALLED COND LEAVING = 84.0~F; RETURN = 74.0~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 54.3mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 74% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 195.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT LOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:18PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 57.2~F GEN PRESSURE = 584.8mmHgA;TEMP = 309.7~F REFRIGERANT = 53.0~F;SOLUTION = 198.6~F NO OPTIONS INSTALLED COND LEAVING = 83.8~F; RETURN = 74.2~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 54.3mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 195.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:20PM 06/15/18 CHILLED LEAVING= 60.7~F; RETURN= 56.9~F GEN PRESSURE = 583.8mmHgA;TEMP = 310.5~F REFRIGERANT = 52.4~F;SOLUTION = 194.8~F NO OPTIONS INSTALLED COND LEAVING = 83.6~F; RETURN = 74.3~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 54.8mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 195.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:22PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 56.7~F GEN PRESSURE = 598.3mmHgA;TEMP = 311.3~F REFRIGERANT = 51.3~F;SOLUTION = 193.8~F NO OPTIONS INSTALLED COND LEAVING = 86.3~F; RETURN = 77.3~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 55.8mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 195.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:24PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 57.2~F GEN PRESSURE = 605.0mmHgA;TEMP = 310.5~F REFRIGERANT = 50.5~F;SOLUTION = 194.6~F NO OPTIONS INSTALLED COND LEAVING = 86.8~F; RETURN = 77.2~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 56.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:25PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 57.1~F GEN PRESSURE = 606.6mmHgA;TEMP = 310.5~F REFRIGERANT = 50.3~F;SOLUTION = 195.3~F NO OPTIONS INSTALLED COND LEAVING = 86.5~F; RETURN = 77.0~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:25PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 56.9~F GEN PRESSURE = 606.6mmHgA;TEMP = 310.5~F REFRIGERANT = 50.0~F;SOLUTION = 195.6~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 77.5~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 2:26PM 06/15/18 CHILLED LEAVING= 60.6~F; RETURN= 57.1~F GEN PRESSURE = 607.6mmHgA;TEMP = 310.9~F REFRIGERANT = 49.5~F;SOLUTION = 195.9~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 77.5~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28110; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC