HISTORY LOG 1 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 3:54PM 06/15/18 CHILLED LEAVING= 48.5~F; RETURN= 52.7~F GEN PRESSURE = 570.9mmHgA;TEMP = 313.0~F REFRIGERANT = 48.9~F;SOLUTION = 205.0~F NO OPTIONS INSTALLED COND LEAVING = 88.0~F; RETURN = 80.4~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 68.8mmHgA OPER. HOURS =28112; START COUNTER = 805 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 49% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 70% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 199.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - HIGH GEN PRESSURE OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC FRI 3:54PM SOLUTION PUMP OVERLOADS OPEN HISTORY LOG 2 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:21PM 06/15/18 CHILLED LEAVING= 61.4~F; RETURN= 58.5~F GEN PRESSURE = 446.8mmHgA;TEMP = 302.8~F REFRIGERANT = 56.6~F;SOLUTION = 195.6~F NO OPTIONS INSTALLED COND LEAVING = 87.2~F; RETURN = 78.7~F PURGE PUMP PRESSURE = 61.5mmHgA PURGE TANK PRESSURE = 30.5mmHgA OPER. HOURS =28110; START COUNTER = 803 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 10% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.4% 2ND STAGE LVG REFRIG TEMP = 189.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC FRI 1:21PM COND FLOW SWITCH - AUTOSTART HISTORY LOG 3 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 1:19PM 06/15/18 CHILLED LEAVING= 61.4~F; RETURN= 58.5~F GEN PRESSURE = 587.9mmHgA;TEMP = 302.4~F REFRIGERANT = 57.0~F;SOLUTION = 200.7~F NO OPTIONS INSTALLED COND LEAVING = 92.5~F; RETURN = 78.9~F PURGE PUMP PRESSURE = 62.1mmHgA PURGE TANK PRESSURE = 30.0mmHgA OPER. HOURS =28110; START COUNTER = 802 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 81% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.1% 2ND STAGE LVG REFRIG TEMP = 195.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 4; TOTAL= 181 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - ON POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC FRI 1:19PM COND FLOW SWITCH - AUTOSTART HISTORY LOG 4 ;SYS 0 c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:41PM 08/25/17 CHILLED LEAVING= 43.9~F; RETURN= 50.5~F GEN PRESSURE = 347.5mmHgA;TEMP = 269.7~F REFRIGERANT = 42.4~F;SOLUTION = 174.5~F NO OPTIONS INSTALLED COND LEAVING = 92.9~F; RETURN = 84.3~F PURGE PUMP PRESSURE = 11.9mmHgA PURGE TANK PRESSURE = 33.1mmHgA OPER. HOURS =28103; START COUNTER = 799 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 62% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 169.3~F REMOTE MODE READY TO START RELAY - ON CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 1; TOTAL= 178 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN-LEAVING CHILLED WATER CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC WED 4:58PM CHILLED WATER FLOW SWITCH YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:52PM 06/15/18 CHILLED LEAVING= 49.0~F; RETURN= 53.3~F GEN PRESSURE = 558.5mmHgA;TEMP = 298.6~F REFRIGERANT = 49.9~F;SOLUTION = 202.2~F NO OPTIONS INSTALLED COND LEAVING = 85.6~F; RETURN = 78.5~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 44.0mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 193.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 5:56PM 06/15/18 CHILLED LEAVING= 48.9~F; RETURN= 53.7~F GEN PRESSURE = 550.7mmHgA;TEMP = 297.2~F REFRIGERANT = 49.7~F;SOLUTION = 200.9~F NO OPTIONS INSTALLED COND LEAVING = 85.0~F; RETURN = 78.5~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 46.0mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.5% 2ND STAGE LVG REFRIG TEMP = 192.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 6:02PM 06/15/18 CHILLED LEAVING= 48.9~F; RETURN= 54.0~F GEN PRESSURE = 539.3mmHgA;TEMP = 294.8~F REFRIGERANT = 49.2~F;SOLUTION = 197.6~F NO OPTIONS INSTALLED COND LEAVING = 85.2~F; RETURN = 78.0~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 49.1mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 191.9~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 6:03PM 06/15/18 CHILLED LEAVING= 49.0~F; RETURN= 53.7~F GEN PRESSURE = 535.7mmHgA;TEMP = 294.1~F REFRIGERANT = 49.2~F;SOLUTION = 196.9~F NO OPTIONS INSTALLED COND LEAVING = 85.2~F; RETURN = 77.7~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 49.6mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 191.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 6:07PM 06/15/18 CHILLED LEAVING= 48.8~F; RETURN= 53.6~F GEN PRESSURE = 530.0mmHgA;TEMP = 292.7~F REFRIGERANT = 49.2~F;SOLUTION = 196.4~F NO OPTIONS INSTALLED COND LEAVING = 84.9~F; RETURN = 77.9~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 51.2mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.2% 2ND STAGE LVG REFRIG TEMP = 191.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 6:08PM 06/15/18 CHILLED LEAVING= 48.8~F; RETURN= 53.4~F GEN PRESSURE = 530.0mmHgA;TEMP = 292.7~F REFRIGERANT = 49.1~F;SOLUTION = 196.1~F NO OPTIONS INSTALLED COND LEAVING = 85.0~F; RETURN = 77.7~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 51.7mmHgA OPER. HOURS =28114; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.0% 2ND STAGE LVG REFRIG TEMP = 191.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:08PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC