STRONG ADJUSTED TO 6 TURNS V28 YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:10PM 06/15/18 CHILLED LEAVING= 43.4~F; RETURN= 50.2~F GEN PRESSURE = 586.9mmHgA;TEMP = 313.0~F REFRIGERANT = 44.1~F;SOLUTION = 190.9~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 6.2mmHgA PURGE TANK PRESSURE = 49.6mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 196.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC V28 ADJUSTED TO 5 TURNS YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:12PM 06/15/18 CHILLED LEAVING= 43.3~F; RETURN= 50.2~F GEN PRESSURE = 584.8mmHgA;TEMP = 312.6~F REFRIGERANT = 43.9~F;SOLUTION = 190.4~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 50.7mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 195.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC V28 ADJUSTED TO 4 TURNS YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:14PM 06/15/18 CHILLED LEAVING= 43.2~F; RETURN= 50.5~F GEN PRESSURE = 582.3mmHgA;TEMP = 311.7~F REFRIGERANT = 43.9~F;SOLUTION = 190.7~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 51.2mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 195.4~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC V28 ADJUSTED TO 3 TURNS YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:15PM 06/15/18 CHILLED LEAVING= 43.2~F; RETURN= 50.1~F GEN PRESSURE = 580.2mmHgA;TEMP = 311.7~F REFRIGERANT = 43.8~F;SOLUTION = 190.1~F NO OPTIONS INSTALLED COND LEAVING = 93.7~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 51.7mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 195.4~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC V28 ADJUST TO 2 TURNS YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:17PM 06/15/18 CHILLED LEAVING= 43.1~F; RETURN= 50.2~F GEN PRESSURE = 577.6mmHgA;TEMP = 311.3~F REFRIGERANT = 43.7~F;SOLUTION = 190.1~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 52.7mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 195.1~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC V28 ADJUSTED TO 1 TURN YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:18PM 06/15/18 CHILLED LEAVING= 43.1~F; RETURN= 50.2~F GEN PRESSURE = 572.4mmHgA;TEMP = 310.9~F REFRIGERANT = 43.5~F;SOLUTION = 191.2~F NO OPTIONS INSTALLED COND LEAVING = 93.7~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 6.2mmHgA PURGE TANK PRESSURE = 53.3mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 194.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC V28 aadjusted to 1/2 turn \ YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:22PM 06/15/18 CHILLED LEAVING= 43.0~F; RETURN= 50.2~F GEN PRESSURE = 562.1mmHgA;TEMP = 310.9~F REFRIGERANT = 43.7~F;SOLUTION = 194.0~F NO OPTIONS INSTALLED COND LEAVING = 94.3~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 55.3mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 64.3% 2ND STAGE LVG REFRIG TEMP = 191.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:23PM 06/15/18 CHILLED LEAVING= 42.9~F; RETURN= 50.1~F GEN PRESSURE = 570.9mmHgA;TEMP = 309.7~F REFRIGERANT = 43.5~F;SOLUTION = 193.3~F NO OPTIONS INSTALLED COND LEAVING = 94.7~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 55.8mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 64.0% 2ND STAGE LVG REFRIG TEMP = 192.9~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:25PM 06/15/18 CHILLED LEAVING= 42.9~F; RETURN= 50.1~F GEN PRESSURE = 574.5mmHgA;TEMP = 309.3~F REFRIGERANT = 43.2~F;SOLUTION = 194.0~F NO OPTIONS INSTALLED COND LEAVING = 93.7~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 6.2mmHgA PURGE TANK PRESSURE = 56.9mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 194.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:28PM 06/15/18 CHILLED LEAVING= 42.8~F; RETURN= 49.9~F GEN PRESSURE = 563.1mmHgA;TEMP = 308.9~F REFRIGERANT = 43.4~F;SOLUTION = 195.9~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 58.4mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 194.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:29PM 06/15/18 CHILLED LEAVING= 42.8~F; RETURN= 49.9~F GEN PRESSURE = 562.1mmHgA;TEMP = 308.5~F REFRIGERANT = 43.2~F;SOLUTION = 195.9~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 58.9mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 194.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:29PM 06/15/18 CHILLED LEAVING= 42.8~F; RETURN= 49.9~F GEN PRESSURE = 561.6mmHgA;TEMP = 307.8~F REFRIGERANT = 43.1~F;SOLUTION = 195.6~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 59.5mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.4% 2ND STAGE LVG REFRIG TEMP = 193.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:31PM 06/15/18 CHILLED LEAVING= 42.6~F; RETURN= 49.6~F GEN PRESSURE = 559.5mmHgA;TEMP = 307.8~F REFRIGERANT = 42.8~F;SOLUTION = 195.3~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 60.5mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.4% 2ND STAGE LVG REFRIG TEMP = 193.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:34PM 06/15/18 CHILLED LEAVING= 42.6~F; RETURN= 49.6~F GEN PRESSURE = 558.5mmHgA;TEMP = 307.4~F REFRIGERANT = 42.8~F;SOLUTION = 194.6~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 6.2mmHgA PURGE TANK PRESSURE = 29.0mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 193.5~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:35PM 06/15/18 CHILLED LEAVING= 42.5~F; RETURN= 50.1~F GEN PRESSURE = 557.4mmHgA;TEMP = 307.0~F REFRIGERANT = 42.9~F;SOLUTION = 194.6~F NO OPTIONS INSTALLED COND LEAVING = 94.1~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 6.2mmHgA PURGE TANK PRESSURE = 29.5mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 193.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:39PM 06/15/18 CHILLED LEAVING= 42.4~F; RETURN= 49.8~F GEN PRESSURE = 559.5mmHgA;TEMP = 304.0~F REFRIGERANT = 42.5~F;SOLUTION = 191.2~F NO OPTIONS INSTALLED COND LEAVING = 94.5~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 32.1mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 193.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:41PM 06/15/18 CHILLED LEAVING= 42.4~F; RETURN= 50.1~F GEN PRESSURE = 559.5mmHgA;TEMP = 302.0~F REFRIGERANT = 42.7~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 33.1mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.4% 2ND STAGE LVG REFRIG TEMP = 193.5~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:44PM 06/15/18 CHILLED LEAVING= 42.4~F; RETURN= 49.5~F GEN PRESSURE = 554.8mmHgA;TEMP = 296.8~F REFRIGERANT = 42.5~F;SOLUTION = 188.8~F NO OPTIONS INSTALLED COND LEAVING = 94.1~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 34.6mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.4% 2ND STAGE LVG REFRIG TEMP = 193.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:47PM 06/15/18 CHILLED LEAVING= 42.3~F; RETURN= 49.2~F GEN PRESSURE = 552.8mmHgA;TEMP = 296.5~F REFRIGERANT = 42.5~F;SOLUTION = 188.8~F NO OPTIONS INSTALLED COND LEAVING = 93.5~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 36.2mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.3% 2ND STAGE LVG REFRIG TEMP = 193.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:51PM 06/15/18 CHILLED LEAVING= 42.3~F; RETURN= 49.2~F GEN PRESSURE = 563.1mmHgA;TEMP = 297.5~F REFRIGERANT = 42.7~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 94.3~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 38.3mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.5% 2ND STAGE LVG REFRIG TEMP = 193.5~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:52PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.8~F GEN PRESSURE = 567.3mmHgA;TEMP = 298.6~F REFRIGERANT = 42.4~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 94.7~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 38.8mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.7% 2ND STAGE LVG REFRIG TEMP = 194.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:53PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.3~F GEN PRESSURE = 567.3mmHgA;TEMP = 299.8~F REFRIGERANT = 42.4~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 94.9~F; RETURN = 79.9~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 39.3mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 61.8% 2ND STAGE LVG REFRIG TEMP = 193.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:54PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.2~F GEN PRESSURE = 567.8mmHgA;TEMP = 301.7~F REFRIGERANT = 42.7~F;SOLUTION = 188.8~F NO OPTIONS INSTALLED COND LEAVING = 94.9~F; RETURN = 79.9~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 39.8mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.0% 2ND STAGE LVG REFRIG TEMP = 194.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:56PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.3~F GEN PRESSURE = 567.8mmHgA;TEMP = 303.2~F REFRIGERANT = 42.7~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 94.9~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 40.9mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.5% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:59PM 06/15/18 CHILLED LEAVING= 42.3~F; RETURN= 49.3~F GEN PRESSURE = 570.9mmHgA;TEMP = 305.5~F REFRIGERANT = 42.4~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 94.9~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 41.9mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:03PM 06/15/18 CHILLED LEAVING= 41.8~F; RETURN= 49.0~F GEN PRESSURE = 571.9mmHgA;TEMP = 308.1~F REFRIGERANT = 42.4~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 95.1~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 44.5mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:05PM 06/15/18 CHILLED LEAVING= 42.0~F; RETURN= 49.5~F GEN PRESSURE = 573.5mmHgA;TEMP = 308.1~F REFRIGERANT = 42.2~F;SOLUTION = 188.8~F NO OPTIONS INSTALLED COND LEAVING = 95.1~F; RETURN = 79.9~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 45.0mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 194.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:10PM 06/15/18 CHILLED LEAVING= 42.1~F; RETURN= 49.6~F GEN PRESSURE = 571.9mmHgA;TEMP = 310.5~F REFRIGERANT = 42.1~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 95.1~F; RETURN = 79.9~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 47.6mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.7% 2ND STAGE LVG REFRIG TEMP = 194.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:11PM 06/15/18 CHILLED LEAVING= 42.0~F; RETURN= 49.3~F GEN PRESSURE = 572.4mmHgA;TEMP = 310.5~F REFRIGERANT = 41.9~F;SOLUTION = 188.8~F NO OPTIONS INSTALLED COND LEAVING = 95.3~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 4.1mmHgA PURGE TANK PRESSURE = 48.1mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 194.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:17PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.6~F GEN PRESSURE = 572.4mmHgA;TEMP = 311.3~F REFRIGERANT = 42.4~F;SOLUTION = 188.8~F NO OPTIONS INSTALLED COND LEAVING = 95.5~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 50.7mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 194.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:23PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.6~F GEN PRESSURE = 570.9mmHgA;TEMP = 311.7~F REFRIGERANT = 42.2~F;SOLUTION = 189.6~F NO OPTIONS INSTALLED COND LEAVING = 95.7~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 53.8mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:25PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.6~F GEN PRESSURE = 570.9mmHgA;TEMP = 311.7~F REFRIGERANT = 42.4~F;SOLUTION = 189.4~F NO OPTIONS INSTALLED COND LEAVING = 96.0~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 54.3mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:29PM 06/15/18 CHILLED LEAVING= 42.2~F; RETURN= 49.6~F GEN PRESSURE = 567.8mmHgA;TEMP = 311.7~F REFRIGERANT = 42.1~F;SOLUTION = 189.4~F NO OPTIONS INSTALLED COND LEAVING = 95.7~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 56.4mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 194.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:33PM 06/15/18 CHILLED LEAVING= 42.1~F; RETURN= 49.8~F GEN PRESSURE = 574.5mmHgA;TEMP = 311.3~F REFRIGERANT = 42.4~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 96.8~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 5.2mmHgA PURGE TANK PRESSURE = 58.4mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:35PM 06/15/18 CHILLED LEAVING= 42.1~F; RETURN= 49.8~F GEN PRESSURE = 577.6mmHgA;TEMP = 310.5~F REFRIGERANT = 42.2~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 96.8~F; RETURN = 81.3~F PURGE PUMP PRESSURE = 5.2mmHgA PURGE TANK PRESSURE = 58.9mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.7% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:36PM 06/15/18 CHILLED LEAVING= 42.1~F; RETURN= 50.2~F GEN PRESSURE = 577.6mmHgA;TEMP = 310.1~F REFRIGERANT = 42.4~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 96.6~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 5.2mmHgA PURGE TANK PRESSURE = 59.5mmHgA OPER. HOURS =28117; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.6% 2ND STAGE LVG REFRIG TEMP = 194.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:38PM 06/15/18 CHILLED LEAVING= 42.0~F; RETURN= 49.6~F GEN PRESSURE = 576.6mmHgA;TEMP = 309.3~F REFRIGERANT = 42.2~F;SOLUTION = 189.6~F NO OPTIONS INSTALLED COND LEAVING = 96.6~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 4.1mmHgA PURGE TANK PRESSURE = 29.5mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 194.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:41PM 06/15/18 CHILLED LEAVING= 42.1~F; RETURN= 49.9~F GEN PRESSURE = 575.5mmHgA;TEMP = 308.9~F REFRIGERANT = 42.4~F;SOLUTION = 189.1~F NO OPTIONS INSTALLED COND LEAVING = 96.6~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 2.6mmHgA PURGE TANK PRESSURE = 31.0mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.4% 2ND STAGE LVG REFRIG TEMP = 194.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:47PM 06/15/18 CHILLED LEAVING= 41.9~F; RETURN= 49.5~F GEN PRESSURE = 571.9mmHgA;TEMP = 308.1~F REFRIGERANT = 41.8~F;SOLUTION = 188.1~F NO OPTIONS INSTALLED COND LEAVING = 96.4~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 33.6mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 194.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:50PM 06/15/18 CHILLED LEAVING= 41.8~F; RETURN= 49.3~F GEN PRESSURE = 567.8mmHgA;TEMP = 307.4~F REFRIGERANT = 42.1~F;SOLUTION = 188.1~F NO OPTIONS INSTALLED COND LEAVING = 96.4~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 35.2mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 194.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:53PM 06/15/18 CHILLED LEAVING= 41.8~F; RETURN= 49.3~F GEN PRESSURE = 566.2mmHgA;TEMP = 306.6~F REFRIGERANT = 42.1~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 36.2mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 193.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:53PM 06/15/18 CHILLED LEAVING= 41.8~F; RETURN= 49.5~F GEN PRESSURE = 566.2mmHgA;TEMP = 307.0~F REFRIGERANT = 41.9~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 36.7mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 194.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 9:59PM 06/15/18 CHILLED LEAVING= 41.8~F; RETURN= 49.8~F GEN PRESSURE = 561.6mmHgA;TEMP = 305.5~F REFRIGERANT = 41.8~F;SOLUTION = 188.6~F NO OPTIONS INSTALLED COND LEAVING = 95.3~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 39.3mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.1% 2ND STAGE LVG REFRIG TEMP = 193.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:01PM 06/15/18 CHILLED LEAVING= 41.8~F; RETURN= 49.5~F GEN PRESSURE = 560.5mmHgA;TEMP = 305.5~F REFRIGERANT = 41.6~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 96.4~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 40.3mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.9% 2ND STAGE LVG REFRIG TEMP = 193.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:05PM 06/15/18 CHILLED LEAVING= 41.9~F; RETURN= 49.8~F GEN PRESSURE = 557.4mmHgA;TEMP = 304.7~F REFRIGERANT = 41.8~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 96.0~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 42.4mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 193.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:09PM 06/15/18 CHILLED LEAVING= 41.7~F; RETURN= 49.3~F GEN PRESSURE = 555.9mmHgA;TEMP = 304.3~F REFRIGERANT = 41.9~F;SOLUTION = 188.3~F NO OPTIONS INSTALLED COND LEAVING = 97.2~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 44.0mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 192.9~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:11PM 06/15/18 CHILLED LEAVING= 41.6~F; RETURN= 49.8~F GEN PRESSURE = 552.8mmHgA;TEMP = 304.7~F REFRIGERANT = 42.1~F;SOLUTION = 188.1~F NO OPTIONS INSTALLED COND LEAVING = 96.0~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 44.5mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.1% 2ND STAGE LVG REFRIG TEMP = 192.9~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:17PM 06/15/18 CHILLED LEAVING= 41.6~F; RETURN= 49.8~F GEN PRESSURE = 548.1mmHgA;TEMP = 304.0~F REFRIGERANT = 41.9~F;SOLUTION = 187.8~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 47.1mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.1% 2ND STAGE LVG REFRIG TEMP = 192.4~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC