@ 4110GPM Cond Flow @ 2500 GPM Chilled Water YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS TUE 11:16AM 05/24/16 CHILLED LEAVING= 45.0~F; RETURN= 51.0~F GEN PRESSURE = 251.8mmHgA;TEMP = 283.3~F REFRIGERANT = 44.1~F;SOLUTION = 172.6~F NO OPTIONS INSTALLED COND LEAVING = 86.8~F; RETURN = 79.4~F PURGE PUMP PRESSURE = 51.2mmHgA PURGE TANK PRESSURE = 54.8mmHgA OPER. HOURS =24147; START COUNTER = 779 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 48% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 66.4% 2ND STAGE LVG REFRIG TEMP = 160.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 2; TOTAL= 141 OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - PRESS STATUS WARNING - AUTO PURGE FAILURE WARNING - SOL'N CONCENTRATION OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC TUE 11:16AM-HIGH SOLUTION CONCENTRATION