@ 4110GPM Cond Flow @ 2500 GPM Chilled Water YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 9:52AM 05/25/16 CHILLED LEAVING= 50.2~F; RETURN= 52.7~F GEN PRESSURE = 170.1mmHgA;TEMP = 225.0~F REFRIGERANT = 50.2~F;SOLUTION = 138.5~F NO OPTIONS INSTALLED COND LEAVING = 83.4~F; RETURN = 75.8~F PURGE PUMP PRESSURE = 44.0mmHgA PURGE TANK PRESSURE = 55.3mmHgA OPER. HOURS =24147; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 58.5% 2ND STAGE LVG REFRIG TEMP = 143.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:09AM 05/25/16 CHILLED LEAVING= 46.2~F; RETURN= 51.1~F GEN PRESSURE = 266.8mmHgA;TEMP = 274.2~F REFRIGERANT = 44.1~F;SOLUTION = 168.0~F NO OPTIONS INSTALLED COND LEAVING = 86.1~F; RETURN = 76.5~F PURGE PUMP PRESSURE = 0.0mmHgA PURGE TANK PRESSURE = 57.4mmHgA OPER. HOURS =24147; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 69% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.3% 2ND STAGE LVG REFRIG TEMP = 158.1~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:12AM 05/25/16 CHILLED LEAVING= 45.6~F; RETURN= 51.0~F GEN PRESSURE = 275.1mmHgA;TEMP = 277.3~F REFRIGERANT = 43.8~F;SOLUTION = 171.2~F NO OPTIONS INSTALLED COND LEAVING = 86.5~F; RETURN = 76.7~F PURGE PUMP PRESSURE = 0.0mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =24147; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.6% 2ND STAGE LVG REFRIG TEMP = 158.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:13AM 05/25/16 CHILLED LEAVING= 45.4~F; RETURN= 50.8~F GEN PRESSURE = 278.2mmHgA;TEMP = 277.3~F REFRIGERANT = 43.7~F;SOLUTION = 172.3~F NO OPTIONS INSTALLED COND LEAVING = 86.8~F; RETURN = 76.8~F PURGE PUMP PRESSURE = 0.0mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =24147; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.5% 2ND STAGE LVG REFRIG TEMP = 159.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:23AM 05/25/16 CHILLED LEAVING= 43.9~F; RETURN= 49.5~F GEN PRESSURE = 286.0mmHgA;TEMP = 270.3~F REFRIGERANT = 42.5~F;SOLUTION = 179.5~F NO OPTIONS INSTALLED COND LEAVING = 86.5~F; RETURN = 76.7~F PURGE PUMP PRESSURE > 219.8mmHgA PURGE TANK PRESSURE = 59.5mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 66% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 63.1% 2ND STAGE LVG REFRIG TEMP = 163.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:30AM 05/25/16 CHILLED LEAVING= 43.4~F; RETURN= 49.2~F GEN PRESSURE = 295.3mmHgA;TEMP = 283.0~F REFRIGERANT = 41.8~F;SOLUTION = 180.6~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 76.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 60.0mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.3% 2ND STAGE LVG REFRIG TEMP = 165.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:32AM 05/25/16 CHILLED LEAVING= 43.6~F; RETURN= 49.5~F GEN PRESSURE = 299.9mmHgA;TEMP = 284.9~F REFRIGERANT = 41.8~F;SOLUTION = 181.1~F NO OPTIONS INSTALLED COND LEAVING = 87.0~F; RETURN = 76.8~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 60.5mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.6% 2ND STAGE LVG REFRIG TEMP = 165.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:36AM 05/25/16 CHILLED LEAVING= 43.8~F; RETURN= 49.9~F GEN PRESSURE = 313.4mmHgA;TEMP = 287.2~F REFRIGERANT = 41.9~F;SOLUTION = 181.6~F NO OPTIONS INSTALLED COND LEAVING = 88.0~F; RETURN = 77.3~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 61.0mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 75% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.5% 2ND STAGE LVG REFRIG TEMP = 167.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:37AM 05/25/16 CHILLED LEAVING= 43.7~F; RETURN= 49.8~F GEN PRESSURE = 315.9mmHgA;TEMP = 287.2~F REFRIGERANT = 41.8~F;SOLUTION = 181.6~F NO OPTIONS INSTALLED COND LEAVING = 87.8~F; RETURN = 77.3~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 61.0mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 75% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.5% 2ND STAGE LVG REFRIG TEMP = 168.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:43AM 05/25/16 CHILLED LEAVING= 43.0~F; RETURN= 49.3~F GEN PRESSURE = 270.4mmHgA;TEMP = 289.9~F REFRIGERANT = 42.1~F;SOLUTION = 183.3~F NO OPTIONS INSTALLED COND LEAVING = 85.8~F; RETURN = 76.8~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 62.1mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 48% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 66.2% 2ND STAGE LVG REFRIG TEMP = 166.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - SOL'N CONCENTRATION OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:44AM 05/25/16 CHILLED LEAVING= 43.2~F; RETURN= 49.3~F GEN PRESSURE = 258.0mmHgA;TEMP = 287.2~F REFRIGERANT = 41.9~F;SOLUTION = 182.7~F NO OPTIONS INSTALLED COND LEAVING = 85.4~F; RETURN = 76.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 62.1mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 48% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 66.4% 2ND STAGE LVG REFRIG TEMP = 163.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - SOL'N CONCENTRATION OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC WED 10:44AM-HIGH SOLUTION CONCENTRATION YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:44AM 05/25/16 CHILLED LEAVING= 43.2~F; RETURN= 49.3~F GEN PRESSURE = 258.0mmHgA;TEMP = 287.2~F REFRIGERANT = 41.9~F;SOLUTION = 182.7~F NO OPTIONS INSTALLED COND LEAVING = 85.4~F; RETURN = 76.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 62.1mmHgA OPER. HOURS =24148; START COUNTER = 780 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 48% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 66.4% 2ND STAGE LVG REFRIG TEMP = 163.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 0; TOTAL= 141 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - PRESS STATUS WARNING - SOL'N CONCENTRATION OVERRIDE WARNING RELAY - ON SAFETY SHUTDOWN RELAY - ON CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC WED 10:52AM-HIGH SOLUTION CONCENTRATION YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 10:56AM 05/25/16 CHILLED LEAVING= 48.2~F; RETURN= 52.2~F GEN PRESSURE = 96.2mmHgA;TEMP = 232.6~F REFRIGERANT = 43.5~F;SOLUTION = 175.9~F NO OPTIONS INSTALLED COND LEAVING = 79.6~F; RETURN = 76.3~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 63.6mmHgA OPER. HOURS =24148; START COUNTER = 782 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 26% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.7% 2ND STAGE LVG REFRIG TEMP = 122.0~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 1; TOTAL= 142 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 11:00AM 05/25/16 CHILLED LEAVING= 49.2~F; RETURN= 52.2~F GEN PRESSURE = 142.7mmHgA;TEMP = 223.8~F REFRIGERANT = 44.7~F;SOLUTION = 170.6~F NO OPTIONS INSTALLED COND LEAVING = 79.4~F; RETURN = 76.0~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 63.6mmHgA OPER. HOURS =24148; START COUNTER = 782 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 63% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.5% 2ND STAGE LVG REFRIG TEMP = 127.1~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2002 MAN PURGES LAST 7 DAYS= 1; TOTAL= 142 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC º"eMõ 1; TOTAL= 2003 MAN PURGES LAST 7 DAYS= 1; TOTAL= 142 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 11:18AM 05/25/16 CHILLED LEAVING= 46.0~F; RETURN= 50.8~F GEN PRESSURE = 254.4mmHgA;TEMP = 271.5~F REFRIGERANT = 44.4~F;SOLUTION = 166.8~F NO OPTIONS INSTALLED COND LEAVING = 85.6~F; RETURN = 76.0~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 32.6mmHgA OPER. HOURS =24148; START COUNTER = 782 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 81% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 65.3% 2ND STAGE LVG REFRIG TEMP = 155.4~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2003 MAN PURGES LAST 7 DAYS= 1; TOTAL= 142 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 11:24AM 05/25/16 CHILLED LEAVING= 45.4~F; RETURN= 51.1~F GEN PRESSURE = 272.5mmHgA;TEMP = 275.7~F REFRIGERANT = 43.7~F;SOLUTION = 171.4~F NO OPTIONS INSTALLED COND LEAVING = 86.7~F; RETURN = 76.3~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 32.6mmHgA OPER. HOURS =24149; START COUNTER = 782 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 99% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 64.8% 2ND STAGE LVG REFRIG TEMP = 161.1~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2003 MAN PURGES LAST 7 DAYS= 1; TOTAL= 142 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 11:30AM 05/25/16 CHILLED LEAVING= 45.0~F; RETURN= 50.7~F GEN PRESSURE = 288.5mmHgA;TEMP = 277.6~F REFRIGERANT = 43.2~F;SOLUTION = 175.3~F NO OPTIONS INSTALLED COND LEAVING = 87.2~F; RETURN = 76.7~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 33.1mmHgA OPER. HOURS =24149; START COUNTER = 782 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 99% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 64.5% 2ND STAGE LVG REFRIG TEMP = 163.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2003 MAN PURGES LAST 7 DAYS= 1; TOTAL= 142 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS WED 11:31AM 05/25/16 CHILLED LEAVING= 44.9~F; RETURN= 50.7~F GEN PRESSURE = 291.6mmHgA;TEMP = 277.6~F REFRIGERANT = 43.1~F;SOLUTION = 175.6~F NO OPTIONS INSTALLED COND LEAVING = 87.4~F; RETURN = 76.8~F PURGE PUMP PRESSURE < 0.0mmHgA PURGE TANK PRESSURE = 33.1mmHgA OPER. HOURS =24149; START COUNTER = 782 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 99% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 64.5% 2ND STAGE LVG REFRIG TEMP = 164.1~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2003 MAN PURGES LAST 7 DAYS= 1; TOTAL= 142 OKI STRT=10:00AM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 10:35AM 05/18/16- P.F. DURATION = 0HR, 3MIN,58SEC