YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:05PM 06/15/18 CHILLED LEAVING= 48.0~F; RETURN= 52.4~F GEN PRESSURE = 517.6mmHgA;TEMP = 294.8~F REFRIGERANT = 48.4~F;SOLUTION = 196.4~F NO OPTIONS INSTALLED COND LEAVING = 87.0~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 46.5mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 57% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 60% HI TEMP GENERATOR CONCENTRATION = 61.8% 2ND STAGE LVG REFRIG TEMP = 189.7~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:09PM 06/15/18 CHILLED LEAVING= 47.8~F; RETURN= 52.0~F GEN PRESSURE = 541.4mmHgA;TEMP = 294.8~F REFRIGERANT = 48.6~F;SOLUTION = 194.0~F NO OPTIONS INSTALLED COND LEAVING = 88.7~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 48.6mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 63% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.7% 2ND STAGE LVG REFRIG TEMP = 190.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:09PM 06/15/18 CHILLED LEAVING= 47.9~F; RETURN= 52.2~F GEN PRESSURE = 551.7mmHgA;TEMP = 295.4~F REFRIGERANT = 48.1~F;SOLUTION = 193.3~F NO OPTIONS INSTALLED COND LEAVING = 90.2~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 48.6mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 63% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.6% 2ND STAGE LVG REFRIG TEMP = 191.3~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 1:00PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:11PM 06/15/18 CHILLED LEAVING= 47.9~F; RETURN= 52.2~F GEN PRESSURE = 561.6mmHgA;TEMP = 297.9~F REFRIGERANT = 48.3~F;SOLUTION = 196.6~F NO OPTIONS INSTALLED COND LEAVING = 90.0~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 49.6mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 63% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 61.7% 2ND STAGE LVG REFRIG TEMP = 193.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:17PM 06/15/18 CHILLED LEAVING= 47.0~F; RETURN= 51.4~F GEN PRESSURE = 575.5mmHgA;TEMP = 302.8~F REFRIGERANT = 47.8~F;SOLUTION = 190.9~F NO OPTIONS INSTALLED COND LEAVING = 89.7~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 52.2mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 63% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.3% 2ND STAGE LVG REFRIG TEMP = 194.6~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:18PM 06/15/18 CHILLED LEAVING= 46.9~F; RETURN= 51.7~F GEN PRESSURE = 577.6mmHgA;TEMP = 303.2~F REFRIGERANT = 48.1~F;SOLUTION = 190.7~F NO OPTIONS INSTALLED COND LEAVING = 89.5~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 52.7mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 63% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 65% HI TEMP GENERATOR CONCENTRATION = 62.4% 2ND STAGE LVG REFRIG TEMP = 194.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:22PM 06/15/18 CHILLED LEAVING= 46.6~F; RETURN= 51.4~F GEN PRESSURE = 602.9mmHgA;TEMP = 307.4~F REFRIGERANT = 47.8~F;SOLUTION = 196.4~F NO OPTIONS INSTALLED COND LEAVING = 91.2~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 54.8mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:23PM 06/15/18 CHILLED LEAVING= 46.6~F; RETURN= 51.3~F GEN PRESSURE = 604.0mmHgA;TEMP = 308.1~F REFRIGERANT = 47.4~F;SOLUTION = 197.4~F NO OPTIONS INSTALLED COND LEAVING = 91.2~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 55.3mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:24PM 06/15/18 CHILLED LEAVING= 46.6~F; RETURN= 51.6~F GEN PRESSURE = 606.0mmHgA;TEMP = 308.1~F REFRIGERANT = 47.4~F;SOLUTION = 197.6~F NO OPTIONS INSTALLED COND LEAVING = 91.3~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 55.3mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:25PM 06/15/18 CHILLED LEAVING= 46.6~F; RETURN= 51.3~F GEN PRESSURE = 606.0mmHgA;TEMP = 309.3~F REFRIGERANT = 47.2~F;SOLUTION = 197.4~F NO OPTIONS INSTALLED COND LEAVING = 91.3~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 55.8mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 62.9% 2ND STAGE LVG REFRIG TEMP = 197.1~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:28PM 06/15/18 CHILLED LEAVING= 46.3~F; RETURN= 51.3~F GEN PRESSURE = 607.6mmHgA;TEMP = 310.1~F REFRIGERANT = 47.2~F;SOLUTION = 196.4~F NO OPTIONS INSTALLED COND LEAVING = 91.2~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 197.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:29PM 06/15/18 CHILLED LEAVING= 46.3~F; RETURN= 51.4~F GEN PRESSURE = 607.6mmHgA;TEMP = 310.1~F REFRIGERANT = 47.1~F;SOLUTION = 196.1~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.0% 2ND STAGE LVG REFRIG TEMP = 197.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:31PM 06/15/18 CHILLED LEAVING= 46.1~F; RETURN= 51.0~F GEN PRESSURE = 607.6mmHgA;TEMP = 310.5~F REFRIGERANT = 46.9~F;SOLUTION = 192.0~F NO OPTIONS INSTALLED COND LEAVING = 91.2~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 2.1mmHgA PURGE TANK PRESSURE = 29.5mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.1% 2ND STAGE LVG REFRIG TEMP = 197.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:35PM 06/15/18 CHILLED LEAVING= 45.9~F; RETURN= 51.1~F GEN PRESSURE = 600.9mmHgA;TEMP = 310.9~F REFRIGERANT = 46.5~F;SOLUTION = 193.5~F NO OPTIONS INSTALLED COND LEAVING = 91.0~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 31.5mmHgA OPER. HOURS =28115; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:37PM 06/15/18 CHILLED LEAVING= 45.9~F; RETURN= 51.1~F GEN PRESSURE = 600.4mmHgA;TEMP = 310.9~F REFRIGERANT = 46.6~F;SOLUTION = 195.9~F NO OPTIONS INSTALLED COND LEAVING = 91.7~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 32.6mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:41PM 06/15/18 CHILLED LEAVING= 45.8~F; RETURN= 51.3~F GEN PRESSURE = 599.3mmHgA;TEMP = 310.1~F REFRIGERANT = 46.3~F;SOLUTION = 195.6~F NO OPTIONS INSTALLED COND LEAVING = 91.7~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 1.0mmHgA PURGE TANK PRESSURE = 34.1mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:44PM 06/15/18 CHILLED LEAVING= 45.6~F; RETURN= 50.8~F GEN PRESSURE = 599.3mmHgA;TEMP = 310.5~F REFRIGERANT = 46.2~F;SOLUTION = 195.1~F NO OPTIONS INSTALLED COND LEAVING = 92.1~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 35.7mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:45PM 06/15/18 CHILLED LEAVING= 45.5~F; RETURN= 50.5~F GEN PRESSURE = 597.3mmHgA;TEMP = 310.5~F REFRIGERANT = 46.2~F;SOLUTION = 194.8~F NO OPTIONS INSTALLED COND LEAVING = 91.7~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 36.7mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 67% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 68% HI TEMP GENERATOR CONCENTRATION = 63.2% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:47PM 06/15/18 CHILLED LEAVING= 45.4~F; RETURN= 50.8~F GEN PRESSURE = 600.4mmHgA;TEMP = 310.5~F REFRIGERANT = 45.9~F;SOLUTION = 194.8~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 80.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 37.2mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 70% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 72% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:49PM 06/15/18 CHILLED LEAVING= 45.3~F; RETURN= 51.0~F GEN PRESSURE = 600.4mmHgA;TEMP = 310.9~F REFRIGERANT = 45.9~F;SOLUTION = 194.6~F NO OPTIONS INSTALLED COND LEAVING = 91.5~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 38.8mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 70% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 72% HI TEMP GENERATOR CONCENTRATION = 63.3% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:52PM 06/15/18 CHILLED LEAVING= 45.2~F; RETURN= 51.0~F GEN PRESSURE = 606.6mmHgA;TEMP = 312.1~F REFRIGERANT = 45.7~F;SOLUTION = 193.5~F NO OPTIONS INSTALLED COND LEAVING = 92.9~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 40.3mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 77% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 78% HI TEMP GENERATOR CONCENTRATION = 63.4% 2ND STAGE LVG REFRIG TEMP = 197.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:53PM 06/15/18 CHILLED LEAVING= 45.2~F; RETURN= 50.4~F GEN PRESSURE = 606.6mmHgA;TEMP = 312.6~F REFRIGERANT = 45.7~F;SOLUTION = 193.5~F NO OPTIONS INSTALLED COND LEAVING = 92.9~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 5.2mmHgA PURGE TANK PRESSURE = 40.9mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 77% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 78% HI TEMP GENERATOR CONCENTRATION = 63.5% 2ND STAGE LVG REFRIG TEMP = 197.4~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:59PM 06/15/18 CHILLED LEAVING= 44.4~F; RETURN= 50.5~F GEN PRESSURE = 600.4mmHgA;TEMP = 313.4~F REFRIGERANT = 45.3~F;SOLUTION = 192.2~F NO OPTIONS INSTALLED COND LEAVING = 93.1~F; RETURN = 81.0~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 43.4mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 77% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 78% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 7:59PM 06/15/18 CHILLED LEAVING= 44.3~F; RETURN= 50.8~F GEN PRESSURE = 600.9mmHgA;TEMP = 313.4~F REFRIGERANT = 45.6~F;SOLUTION = 192.2~F NO OPTIONS INSTALLED COND LEAVING = 93.5~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 44.0mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 83% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:01PM 06/15/18 CHILLED LEAVING= 44.0~F; RETURN= 50.4~F GEN PRESSURE = 600.4mmHgA;TEMP = 313.4~F REFRIGERANT = 45.1~F;SOLUTION = 191.4~F NO OPTIONS INSTALLED COND LEAVING = 93.5~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 45.0mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 83% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:02PM 06/15/18 CHILLED LEAVING= 44.0~F; RETURN= 50.2~F GEN PRESSURE = 598.3mmHgA;TEMP = 313.8~F REFRIGERANT = 45.1~F;SOLUTION = 191.2~F NO OPTIONS INSTALLED COND LEAVING = 93.5~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 45.5mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.8% 2ND STAGE LVG REFRIG TEMP = 196.8~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:05PM 06/15/18 CHILLED LEAVING= 43.8~F; RETURN= 50.2~F GEN PRESSURE = 595.2mmHgA;TEMP = 313.8~F REFRIGERANT = 44.8~F;SOLUTION = 191.2~F NO OPTIONS INSTALLED COND LEAVING = 93.5~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 46.5mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:07PM 06/15/18 CHILLED LEAVING= 43.6~F; RETURN= 50.7~F GEN PRESSURE = 592.6mmHgA;TEMP = 313.4~F REFRIGERANT = 44.5~F;SOLUTION = 190.4~F NO OPTIONS INSTALLED COND LEAVING = 93.9~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 48.1mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 196.5~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 8:08PM 06/15/18 CHILLED LEAVING= 43.4~F; RETURN= 49.9~F GEN PRESSURE = 590.5mmHgA;TEMP = 313.4~F REFRIGERANT = 44.5~F;SOLUTION = 190.7~F NO OPTIONS INSTALLED COND LEAVING = 93.7~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 5.7mmHgA PURGE TANK PRESSURE = 48.1mmHgA OPER. HOURS =28116; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 84% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 85% HI TEMP GENERATOR CONCENTRATION = 63.9% 2ND STAGE LVG REFRIG TEMP = 196.2~F REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT HOLDING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC