YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:22PM 06/15/18 CHILLED LEAVING= 41.5~F; RETURN= 49.5~F GEN PRESSURE = 544.5mmHgA;TEMP = 302.8~F REFRIGERANT = 41.6~F;SOLUTION = 187.3~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 49.6mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.9% 2ND STAGE LVG REFRIG TEMP = 191.9~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:29PM 06/15/18 CHILLED LEAVING= 41.5~F; RETURN= 49.6~F GEN PRESSURE = 541.4mmHgA;TEMP = 302.0~F REFRIGERANT = 41.5~F;SOLUTION = 187.6~F NO OPTIONS INSTALLED COND LEAVING = 96.0~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 52.7mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.8% 2ND STAGE LVG REFRIG TEMP = 191.9~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - MAXIMUM COOLING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:32PM 06/15/18 CHILLED LEAVING= 41.5~F; RETURN= 49.3~F GEN PRESSURE = 540.4mmHgA;TEMP = 301.3~F REFRIGERANT = 41.3~F;SOLUTION = 187.3~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 54.3mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 100% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 191.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - UNIT UNLOADING WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:33PM 06/15/18 CHILLED LEAVING= 41.5~F; RETURN= 49.6~F GEN PRESSURE = 539.3mmHgA;TEMP = 300.9~F REFRIGERANT = 41.6~F;SOLUTION = 187.3~F NO OPTIONS INSTALLED COND LEAVING = 96.4~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 54.3mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 89% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 191.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:35PM 06/15/18 CHILLED LEAVING= 41.5~F; RETURN= 49.3~F GEN PRESSURE = 539.3mmHgA;TEMP = 300.9~F REFRIGERANT = 41.3~F;SOLUTION = 186.7~F NO OPTIONS INSTALLED COND LEAVING = 96.4~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 55.3mmHgA OPER. HOURS =28118; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 89% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 191.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 5; TOTAL= 182 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:41PM 06/15/18 CHILLED LEAVING= 41.4~F; RETURN= 49.3~F GEN PRESSURE = 534.7mmHgA;TEMP = 300.5~F REFRIGERANT = 41.5~F;SOLUTION = 187.6~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 57.9mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 89% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 191.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:42PM 06/15/18 CHILLED LEAVING= 41.4~F; RETURN= 49.2~F GEN PRESSURE = 533.6mmHgA;TEMP = 300.5~F REFRIGERANT = 41.6~F;SOLUTION = 187.6~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 58.4mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 89% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 191.1~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:47PM 06/15/18 CHILLED LEAVING= 41.3~F; RETURN= 49.2~F GEN PRESSURE = 532.1mmHgA;TEMP = 300.5~F REFRIGERANT = 41.5~F;SOLUTION = 187.3~F NO OPTIONS INSTALLED COND LEAVING = 96.0~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 60.5mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 89% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 190.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:51PM 06/15/18 CHILLED LEAVING= 41.3~F; RETURN= 49.2~F GEN PRESSURE = 531.1mmHgA;TEMP = 300.1~F REFRIGERANT = 41.3~F;SOLUTION = 187.0~F NO OPTIONS INSTALLED COND LEAVING = 96.4~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 0.5mmHgA PURGE TANK PRESSURE = 62.6mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 89% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 190.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:53PM 06/15/18 CHILLED LEAVING= 41.2~F; RETURN= 49.0~F GEN PRESSURE = 531.1mmHgA;TEMP = 299.8~F REFRIGERANT = 41.2~F;SOLUTION = 187.0~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 81.1~F PURGE PUMP PRESSURE = 1.6mmHgA PURGE TANK PRESSURE = 63.1mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 90% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 190.8~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 0; TOTAL= 2403 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO STRT= 7:11PM INT= .1HRS .1HRS LFT SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 10:56PM 06/15/18 CHILLED LEAVING= 41.0~F; RETURN= 49.0~F GEN PRESSURE = 527.4mmHgA;TEMP = 300.1~F REFRIGERANT = 41.3~F;SOLUTION = 187.3~F NO OPTIONS INSTALLED COND LEAVING = 96.2~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 3.1mmHgA PURGE TANK PRESSURE = 31.5mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 87% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 190.3~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:09PM 06/15/18 CHILLED LEAVING= 40.8~F; RETURN= 49.0~F GEN PRESSURE = 520.7mmHgA;TEMP = 299.0~F REFRIGERANT = 41.3~F;SOLUTION = 187.3~F NO OPTIONS INSTALLED COND LEAVING = 95.7~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 6.7mmHgA PURGE TANK PRESSURE = 37.2mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 87% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 189.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - ON AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:17PM 06/15/18 CHILLED LEAVING= 40.7~F; RETURN= 48.7~F GEN PRESSURE = 515.0mmHgA;TEMP = 299.0~F REFRIGERANT = 40.6~F;SOLUTION = 186.7~F NO OPTIONS INSTALLED COND LEAVING = 96.0~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 9.3mmHgA PURGE TANK PRESSURE = 40.9mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 41.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 86% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 189.5~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:25PM 06/15/18 CHILLED LEAVING= 40.6~F; RETURN= 48.6~F GEN PRESSURE = 513.0mmHgA;TEMP = 299.0~F REFRIGERANT = 40.9~F;SOLUTION = 186.5~F NO OPTIONS INSTALLED COND LEAVING = 96.6~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 11.9mmHgA PURGE TANK PRESSURE = 44.0mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 42.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 86% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.6% 2ND STAGE LVG REFRIG TEMP = 189.2~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:26PM 06/15/18 CHILLED LEAVING= 40.6~F; RETURN= 48.4~F GEN PRESSURE = 510.9mmHgA;TEMP = 298.2~F REFRIGERANT = 40.9~F;SOLUTION = 186.7~F NO OPTIONS INSTALLED COND LEAVING = 96.0~F; RETURN = 80.4~F PURGE PUMP PRESSURE = 12.4mmHgA PURGE TANK PRESSURE = 44.5mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 80% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 188.9~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:30PM 06/15/18 CHILLED LEAVING= 40.5~F; RETURN= 48.7~F GEN PRESSURE = 503.7mmHgA;TEMP = 297.5~F REFRIGERANT = 41.0~F;SOLUTION = 186.5~F NO OPTIONS INSTALLED COND LEAVING = 95.7~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 14.0mmHgA PURGE TANK PRESSURE = 46.0mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 74% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.7% 2ND STAGE LVG REFRIG TEMP = 188.7~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:34PM 06/15/18 CHILLED LEAVING= 40.5~F; RETURN= 48.6~F GEN PRESSURE = 490.2mmHgA;TEMP = 295.8~F REFRIGERANT = 40.4~F;SOLUTION = 186.5~F NO OPTIONS INSTALLED COND LEAVING = 95.1~F; RETURN = 80.3~F PURGE PUMP PRESSURE = 15.5mmHgA PURGE TANK PRESSURE = 48.1mmHgA OPER. HOURS =28119; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 68% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.5% 2ND STAGE LVG REFRIG TEMP = 187.4~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:39PM 06/15/18 CHILLED LEAVING= 40.7~F; RETURN= 48.4~F GEN PRESSURE = 469.5mmHgA;TEMP = 291.7~F REFRIGERANT = 40.6~F;SOLUTION = 185.7~F NO OPTIONS INSTALLED COND LEAVING = 94.5~F; RETURN = 80.6~F PURGE PUMP PRESSURE = 17.6mmHgA PURGE TANK PRESSURE = 50.2mmHgA OPER. HOURS =28120; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 62% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.2% 2ND STAGE LVG REFRIG TEMP = 185.6~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC YORK SYSTEM 0 UPDATE c1993 YORK INTERNATIONAL CORP. VERSION A.01F.12.133.00 TODAY IS FRI 11:43PM 06/15/18 CHILLED LEAVING= 40.8~F; RETURN= 48.1~F GEN PRESSURE = 448.8mmHgA;TEMP = 289.9~F REFRIGERANT = 40.6~F;SOLUTION = 185.7~F NO OPTIONS INSTALLED COND LEAVING = 93.5~F; RETURN = 80.8~F PURGE PUMP PRESSURE = 18.6mmHgA PURGE TANK PRESSURE = 51.7mmHgA OPER. HOURS =28120; START COUNTER = 807 LVG CHILLED WATER SETPOINT = 43.0~F LOW REFRIGERANT TEMP CUTOUT = 35.0~F SELECTED: COOLING ONLY SPRAY SOLUTION PUMP 2 DELAY = 90 SEC. STEAM VALVE POSITION = 59% SETP= 0MIN;START=100%;STOP=100% PRESENT PULLDOWN LIMIT =100%; 0MIN LEFT MAX ALLOWED LOADING = 100% HI TEMP GENERATOR CONCENTRATION = 62.1% 2ND STAGE LVG REFRIG TEMP = 184.1~F S M T W T F S HOLIDAY NOTED BY * REMOTE TEMP SETPOINT RANGE = 20.0~F SUN START = 00:00AM, STOP = 00:00AM MON START = 00:00AM, STOP = 00:00AM TUE START = 00:00AM, STOP = 00:00AM WED START = 00:00AM, STOP = 00:00AM THU START = 00:00AM, STOP = 00:00AM FRI START = 00:00AM, STOP = 00:00AM SAT START = 00:00AM, STOP = 00:00AM HOL START = 00:00AM, STOP = 00:00AM REMOTE MODE READY TO START RELAY - OFF CHILLED WATER PUMP - ON CONDENSER WATER PUMP - ON REFRIGERANT PUMP - ON SOLUTION PUMP - ON SECOND SPRAY SOLUTION PUMP - ON PURGE PUMP - OFF AUTO PURGES LAST 7 DAYS= 1; TOTAL= 2404 MAN PURGES LAST 7 DAYS= 6; TOTAL= 183 WTO AUTO PRINT INTERVAL = NOT PROGRAMMED SYSTEM RUN - AUTO TEMP CONTROL WARNING RELAY - OFF SAFETY SHUTDOWN RELAY - OFF CYCLING SHUTDOWN RELAY - OFF POWER FAILURE AT 12:54PM 06/05/18- P.F. DURATION = 0HR,54MIN,36SEC